Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

User Interface Functionality

The unit has no user-accessible buttons to avoid manipulation of the device in public environments. Installers rely on a pen-shaped magnet to perform tasks related to the installation.

Gliffy
imageAttachmentIdatt108822572
macroId3287473e-b85b-4d42-94b0-5852543abdc7
baseUrlhttps://micropelt.atlassian.net/wiki
nameMLRTPS_English_Flowchart
diagramAttachmentIdatt108331664
containerId109543425
timestamp1675087294584

Setting up a Gateway

In a web browser, navigate to the gateway IP address

  1. Login to the gateway

  2. LoRaWAN, Network Settings, Join Delay 5 seconds

  3. LoRaWan, Network Settings, Max Datarate 5 – SF7BW125
    Click Submit
    Wait for Save and Apply to go red, and then click it

  4. Firewall, Settings, Input Filter Rules
    Add ‘Allow Inbound’

  5. Click Submit

  6. Wait for Save and Apply to go red, and then click it

Pairing the Device with a Room Controller or Gateway

Devices will be accompanied with a spreadsheet containing the following information:

  • Device EUI

  • Join EUI

  • Application Key

The Device EUI is unique to the device and allows identification and communication via LoRaWAN.

The Application Key is randomly generated to ensure secure communication.

To pair a device to a MultiTech gateway:

  1. In a web browser, navigate to the gateway IP address

  2. Login to the gateway

  3. LoRaWAN, Key Management, click Add New

  4. For each device, enter the following details, and then click OK:
    Dev EUI (available in the spreadsheet)
    App EUI (available in the spreadsheet)
    App Key (available in the spreadsheet)
    Class: A
    Device Profile: LW102-OTA-EU868
    Network Profile: DEFAULT-CLASS-A

  5. Click Submit

  6. Wait for Save and Apply to go red, and then click it

Unboxing and Assembly

The product consists of the following

  • Base Plate

  • Main Housing with Battery disconnected

  • Screws and dowels

Use the provided screws and dowels to fix the base plate onto the wall

Connect the battery to the holder and mount the main housing onto the base plate

Attaching and Activating a unit

Before mounting the device onto the wall, be sure that the battery is connected (refer to the above section).

Once the device is mounted

  1. Briefly tap the pen magnet on the micr°pelt logo on the product’s cover

  2. The radio establishes a link to the gateway upon successful completion, a double-beep sounds

  3. The unit is now active

Activation only works when the battery is plugged in for the first time. If performed during normal operation, the product will not show any reaction.

Reset (from Normal Operation only)

The RESET function allows the user to restart the device. It is also useful to restore correct operation should a malfunction occur.

To RESET the device,

  1. Hold the pen magnet to the micr°pelt logo on the product’s cover until a beep sounds

  2. The internal microcontroller will reset and restart

The device is now active