Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

1.

MANUAL TEACH-IN

Set room controller to pairing teach-in mode.
Check the (Refer to user guide of the room controller).
Set EnOcean EEP A5-20-01
(Teach-in through ReMan/ReCom: Datasheet, Installation Signal Remote Commissioning)

2.

TEACH-IN

Turn wheel to the dial left or right to the end stop and hold for 5 seconds until 1x green LED flash and release it again immediately.

Image RemovedImage Added

1x green LED = successful teach- in.
3x red LED = error, teach-in failed .
(Check gateway teach mode and/or repeat procedure.)

3.

INSTALLATION AND REFERENCE RUN

Mount the device on the M30x1,5 valve body, turn the dial to the left or right to the end position to short press the button. Unit The MAV executes a reference run -in sequence and enters normal operation.

Image RemovedImage Added

During the first 10 minutes, the drive MVA sends in a ten-seconds radio communication interval. UnmountedWhen unmounted, the actuator MVA returns to the assembly position. After 1 hour, the keys push buttons lock automatically. Unlocking: Pull-off the rotary dial cover and press both buttons simultaneously for 10 seconds.

4.

ADDITIONAL THINGS TO KNOW

  • Connection nut M30 x 1.5; adapters are available for many other valve types Adapter

  • Valve should be working freely

  • EnOcean Protokoll A5-20-01

  • Energy storage LiFePo4 320 mAh

  • Operating modes: Valve position % or Setpoint temperature °C

  • Freeze protection < 6°C (Valve side sensor)

  • The iTRV becomes active according to the telegram specification and asks for the room controller on the control position or setpoint temperature. The controller then adjusts the valve according to the following response of the room controller.

  • Summer mode: Radio communication interval increased from 10 minutes to 8 hours.

  • Unmounting: To remove the iTRV, turn the dial to left or right until its end position and hold for at least 5 seconds to 1x green LED, wait for motor to stop, then loosen knurled nut and remove iTRV.

  • Recharge battery:
    – Pull back cover straight off without turning
    – Connect micro USB cable.
    – Charging: Yellow LED lights up constantly (approx. 2 hours when battery is empty)
    – Battery charged: Green LED flashes every 3 seconds
    – Disconnect the cable and snap in the lid without turning. The device remains in its current state during and after charging (Active: Activation is not necessary. Off: Activation according to instructions.).