Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Installation with Manual Pairing

1

No

Objective

Button

No.

Action

LED Activity

Reasons for failure

1

Pairing from mounting position (= shipping condition = OFF)

or normal operation (while buttons not locked)

Turn dial to end position

Left OR Right and hold 5 seconds until 1x green or 3x red LED

Unit does pair and remains in mounting position = shipping condition = OFF

If unit is not in mounting position, it moves to mounting position now.

Success: Single green flash

Failure: Triple red flash

Controller or gateway either not present or not in pairing mode, so that pairing fails

2

Mounting

 

 

Mount the actuator before executing run-in sequence and normal operation

 

 

3

Run-in sequence and normal operation from mounting position

Turn to end position

Left OR Right for short press (< 1 second)

Unit executes run-in sequence; radio communication occurs every 10 seconds for 10 minutes, and then reverts to every 10 minutes.

One hour after this action, the pushbutton switches will lock and can only be unlocked, by performing RESET (5.)

Success: Single green flash

Failure: Triple red flash

Motor or gear error

4

Get new target value (while buttons not locked)

Turn to end position

Left OR Right for short press (< 1 second)

Unit immediately gets target value from controller / gateway, then moves to the new target

Success: Single green flash

Failure: Triple red flash

Unit cannot contact the controller or gateway

Deactivation and Reset

5

Return to mounting position

Turn dial to end position

Left OR Right and hold 5 seconds until single green flash

Green LED appears, followed a triple red LED. The device will turn the motor back to mounting position and switch off.

Success: Single green flash followed by triple red flash

 

 

2

6

Deactivate button lock

and

RESET followed by normal operation

Pull the dial straight off and press both buttons simultaneously for 10 seconds.

The unit enters normal operation, assuming it is paired. For 60 min, the unit will accept a 5-second long-press of any button and for 10 minutes, it will run at a 10-second radio communication interval. It contacts the controller / gateway immediately after RESET.

After 10 seconds 1x green (RESET activated),

then 2x red (new start),

after a short break 1x green (normal operation with successful communication) or

3x red (communication error, mounting error)

Unit cannot contact the controller or gateway it has been paired with

or unit has never been paired. Mounting or motor problems