Protocol data overview

Transmit mode from MVA to controller/ gateway/ server

 

Receive mode from controller / gateway / server to MVA

DB3.7…DB3.0 (CV)

Current valve position 0...100%, linear n=0...100

 

DB3.7…DB3.0 (SP)

New valve position (0...100% ~ 0x00…0x64) or Target temperature (0…40°C ~ 0x00…0xFF)

 

Selection with SPS DB1.2

DB2.7

Not used

 

DB2.7…DB2.0 (TMP)

Room temperature from room sensor

(0…40ºC ~ 0xFF…0x00*)

  • for operation with the internal MVA ambient sensor must be set to 0x00

DB2.6 (ENIE)

Active energy harvesting (valve is hot)

 

DB1.7....DB1.4

Not used (set to “zero”)

DB2.5 (ES)

Energy storage sufficiently filled

 

 

DB1.3 (SB)

Summer mode

transmit / receive time interval 8 hours

DB2.4 (BCAP)

Storage capacity sufficient (analog DB_2. Bit_5)

 

DB1.2 (SPS)*1

Setpoint Selection

0: Valve pos. (0…100%)

1: Temp. setpoint (0…40°C)

DB2.3

Not used

 

DB1.1…DB1.0

Not used (set to “zero”)

DB2.2 (FTS)

Temperature sensor failure

 

DB0.7…DB0.4

Not used (set to “zero”)

DB2.1 (DWO)

Window open detection

 

DB0.3 (LRNB)

LRN Bit, defined for data telegram

DB2.0 (ACO)

Motor failure

 

DB0.2…DB0.0

Not used (set to “zero”)

DB1.7…DB1.0 (TMP)

Ambient temperature MVA

(0…40°C ~ 0x00…0xFF)

 

 

 

DB0.7…DB0.4

Not used

 

 

 

DB0.3 (LRNB)

LRN Bit, defined for data telegram

 

 

 

DB0.2…DB0.0

Not used

 

 

 

...