| Installation cycle | Standard operation | Idle state | Radio failure | Forced heating | Freeze Protection | ||||||||
Comments |
| Valve target % Or Room target temperature
| Phases between monitoring and communicating | Uplinks not received by the gateway | Valve opens to 50% (or remains in current position if current position is
| Valve opens to 95% (or remains in current position if current position is
| ||||||||
Trigger | Magnetic switch. Join accept from Gateway, & Device is mounted | Internal timer | Internal timer | From activation: No Gateway connect From standard operation: 3 7 consecutive Gateway communication failures | Battery voltage < 2V | Flow sensor raw temperature
| ||||||||
Radio communication interval (RCI) | 10 seconds for 5 minutes | 5 minutes 10 minutes 60 minutes 120 minutes 480 minutes | OFF | Three times 30 seconds Then once 2 minutes Then 60 minutes | OFF | OFF | ||||||||
Dynamic change of communication interval
| No | Yes | No | No | No | No | ||||||||
Sensors (flow, ambient) | Active, every 10 seconds | Active | OFF
| Active | OFF | Active, every 2 minutes | ||||||||
Freeze protection | Active, every 10 seconds | Active, every 150 seconds | OFF | Active, every 150 seconds | OFF | Active | ||||||||
Motor operation | Reference run. Then active, every 10 seconds | Set Temperature: Active, every 5 minutes Valve Position: According to radio communications | OFF | Active, every 5 minutes | OFF | OFF | ||||||||
Monitoring of battery | Active, every 10 seconds | Active | OFF | Active | Active, every 12 hours | Active, every | ||||||||
Internal temperature controller | If User Mode is Set Point Ambient Temperature: active | If User Mode is Set Point Ambient Temperature: active | OFF | If Safety Mode is Set Point Ambient Temperature: active | OFF | OFF | ||||||||
Default upon activation and no downlinks | Setpoint ambient 20°C | Setpoint ambient 20°C RCI 10 minutes | Setpoint ambient 20°C |
...