...
The P parameter describes the internal multiplier in the temperature control loop (only with SPS bit = 1) for calculating the valve adjustment % value. With setting 30, a valve opening of 19% is calculated for a temperature failure of 1°C (T ACTUAL = 21 ° C and T TARGET = 22 ° C). An internally determined ambient temperature value is used for the internal calculation of the controller when in automatic offset mode, which is why the corresponding valve opening angles are not calculated using the above method.
ReCom device parameter | INDEX | Description |
Ambient to target temp offset [K] | 0 | (0x00) 0 … Auto* (DEFAULT) (0x01) 1 … -3 K (0x02) 2 … -2 K (0x03) 3 … -1 K (0x04) 4 … 0 K (0x05) 5 … +1 K (0x06) 6 … +2 K (0x07) 7 … +3 K … (0x0F) 15 … +11 K |
Radio communication interval [s/min] | 1 | (0x00) 0…Auto * (DEFAULT) (0x01) 1 … 10sec (for debugging only) (0x02) 2 … 2min (0x03) 3 … 5min (0x04) 4 … 10 min (0x05) 5 … 20min (0x06) 6 … 30min * Automatic mode: 2/5/10 minutes interval based on flow temperature and internal storage |
Execute Reference Run | 10 | 0x01 DEFAULT 0x00 |
Auto ambient to target offset parameter | 11 | (0x00 … 0xFF) 0 … 255 MVA008 DEFAULT* 44 (0x2C)
|
Temp.-control loop gain parameter | 12 | (0x00 … 0xFF) 0 … 255 = 10x GAIN DEFAULT 30 = 0x1E |
Battery open circuit voltage (V) | 13 READ ONLY | (0x00 … 0xFF) 0 … 255 = 10x Voltage Example 0x21 = DEZ 33 : 10 = 3,3Volt |
...