Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Parameter

...

Range

...

Ambient operating temperature

...

0 to 40°C, max 70% rH

...

Flow pipe temperature

...

75°C max

...

Transportation & storage temperature range

...

-20 to +65°C, max 70% rH

...

Dimensions (LWH)

...

83 x 60 x 64 mm (63 x 60 x 64 without valve connector)

...

Weight

...

280 g (not including packing)

...

Operation at high altitude

...

Max 2000 m / 6500 ft above sea level

...

Max pin stroke (calibration range)

...

> 5.5 mm

...

Operating pin stroke (0-100%)

...

2.56 mm typical

...

Pin Stroke Resolution

...

Steps of 1%

...

Adjustment speed

...

0.727 mm/s typical

...

Stall force

...

100N

...

Noise level

...

< 35 dB(A) @ 70 N load

...

Radio Communication Interval (default)

...

10 minutes

...

Radio Communication Interval during Installation Cycle

...

10 seconds for 5 minutes

...

Radio Communication attempt Interval (after join fail or 6 consecutive communication fails)

...

3 * 10 seconds

Then 2 minutes

Then 60 minutes

...

Valve protection and Auto-off when active but not installed on valve body

...

Every 6 weeks: Execute run-in sequence.

On pass return to previous position.

On fail enter mounting position, communicate OFF and shut down.

...

Antifreeze

...

Valve side sensor <= 6°C

 

...

Safe position default

...

Depending on Safety Mode:

Either default temperature setpoint

Or default valve position

Default: Setpoint Ambient 20°C

...

Operating Modes

 

...

Valve Position [%]

Target Ambient Temperature (°C)

Default: Valve Position

...

Accuracy of internal valve side temperature sensor

...

±0.5°C

...

Accuracy of internal ambient temperature sensor

...

±0.5ºC

 

...

Default offset of internal valve-side temperature sensor

...

+5K

(Added to the raw sensor value FSRV)

...

Energy storage

...

LTO (Nominal 500mAh)

...

Energy generation minimum requirement

...

90 days / year @ 45ºC flow pipe temperature

...

Battery voltage flag (ES)

...

Battery-low flag will be set

when battery voltage drops below 2.3V

Conformity

...

UKCA:
EN 300 220-2 V3.1.1
EN 301 489-1 V1.9.2
EN 55014-1:2017
EN 55014-2:1997/A1:2001/A2:2008/AC:1992
EN 62479:2010
EN 60335-1:2012/AC:2014/A11:2014
EN IEC 63000:2018

...

Radio specification

868.0 - 868.6 MHz, 14 dBm

...

Include Page
MLRD:Performance Data
MLRD:Performance Data
Include Page
MLRD:MLR003R: Performance Data
MLRD:MLR003R: Performance Data