Flussdiagramm Bedienung

The unit has no user-accessible buttons to avoid manipulation of the device in public environments. Installers rely on a pen-shaped magnet to perform tasks related to the installation.

Gliffy
imageAttachmentId

...

att21659996
macroId

...

8614ffbc-

...

c65b-

...

4215-

...

9844-

...

f2e8be38900c
baseUrlhttps://micropelt.atlassian.net/wiki
name

...

Flussdiagramm Bedienung
diagramAttachmentId

...

att21987512
containerId

...

22249548
timestamp

...

1652613008778

Setting up a Gateway

In a web browser, navigate to the gateway IP address

  1. Login to the gateway

  2. LoRaWAN, Network Settings, Join Delay 5 seconds

  3. LoRaWan, Network Settings, Max Datarate 5 – SF7BW125
    Click Submit
    Wait for Save and Apply to go red, and then click it

  4. Firewall, Settings, Input Filter Rules
    Add ‘Allow Inbound’

  5. Click Submit

  6. Wait for Save and Apply to go red, and then click it

Pairing the Device with a Room Controller or Gateway

Devices will be accompanied with a spreadsheet containing the following information:

...

  1. In a web browser, navigate to the gateway IP address

  2. Login to the gateway

  3. LoRaWAN, Key Management, click Add New

  4. For each device, enter the following details, and then click OK:
    Dev EUI (available in the spreadsheet)
    App EUI (available in the spreadsheet)
    App Key (available in the spreadsheet)
    Class: A
    Device Profile: LW102-OTA-EU868
    Network Profile: DEFAULT-CLASS-A

  5. Click Submit

  6. Wait for Save and Apply to go red, and then click it

Mounting Position and OFF

In mounting position, the plunger inside the valve actuator is fully retracted, so that the unit can easily be attached to a circulation valve. In mounting position, the product is OFF, preserving the charge of the internal energy storage device. This makes it the preferred mode for shipping and storing.

...

 Upon delivery, all new units are in mounting position.

Attaching and Activating a unit

Before attempting to attach a unit to a valve, be sure it is in mounting position (refer to the above section).

...

Activation only works from mounting position. If performed during normal operation, the product will not show any reaction.

Reset (from Normal Operation only)

The RESET function allows access to mounting position. It is also useful to restore correct operation should a malfunction occur.

...

If the device is unmounted, it will go into mounting position and switch OFF

No Reset from Mounting Position

Removal from the Valve

Unscrew the ring nut from the valve and RESET the device. It will move to mounting position and switch OFF.

Temperature Control Loop

To obtain an estimate of the ambient temperature, the device measures the flow temperature every 5 minutes and performs a moving average across the last 30 minutes. It then performs the following computation:

...