BYTE
...
BIT RANGE
...
SIZE
...
OFFSET
...
ABBREV.
...
DETAILS
...
1
...
DB0.7…0.0
...
8
...
0
...
CVP
...
Current Valve Position %
0x00 … 0x64 / 0 … 100%
Res = 1%
...
2
...
DB1.7…1.0
...
8
...
8
...
FSRV
...
Flow Sensor RAW Value °C
0x00 … 0xFF / 0 … 125.0°C
Res = 0.5°C
...
3
...
DB2.7…2.0
...
8
...
16
...
FTMP
...
Flow TEMPERATURE Value °C
Orah footnote | ||
---|---|---|
|
0x00 … 0xFF / 0 … 125.0°C
Res = 0.5°C
...
4
...
DB3.7…3.0
...
8
...
24
...
ASRV
...
Ambient Sensor RAW Value °C
0x00 … 0xFF / 0 … 63.75°C
Res = 0.25°C
...
5
...
DB4.7…4.0
...
8
...
32
...
ATMP
...
Ambient TEMPERATURE Value °C
Orah footnote | ||
---|---|---|
|
0x00 … 0xFF / 0 … 63.75°C
Res = 0.25°C
...
6
...
DB5.7
...
1
...
40
...
...
RESERVED
...
...
DB5.6
...
1
...
41
...
ES
...
Energy Storage is low
1 = Battery is low
...
...
DB5.5
...
1
...
42
...
HA
...
Harvesting
1 = Harvesting is active
...
...
DB5.4
...
1
...
43
...
ASF
...
Ambient Sensor Failure
1 = Sensor Failure
...
...
DB5.3
...
1
...
44
...
FSF
...
Flow Sensor Failure
1 = Sensor Failure
...
...
DB5.2
...
1
...
45
...
RCE
...
Radio Communication Error
1 = Radio Loss
Orah footnote | ||
---|---|---|
|
...
...
DB5.1
...
1
...
46
...
RSS
...
Radio Signal Strength
0 = Normal Radio Signal (RSSI is greater than -100 dBm)
1 = Weak Radio Signal (RSSI is less than -100 dBm)
...
...
DB5.0
...
1
...
47
...
ME
...
Motor
1 = Motor Error
...
7
...
DB6.7…6.0
...
8
...
48
...
STV
...
Storage Voltage V
0x00 … 0xFF / 0 … 5100mV
Res = 20mV
...
8
...
DB7.7…7.0
...
8
...
56
...
ACC
...
Average Current Consumed
0x00 … 0xFF / 0 … 2550µA
Res = 10µA
...
9
...
DB8.7…7.0
...
8
...
64
...
ACG
...
Average Current Generated
Orah footnote | ||
---|---|---|
|
0x00 … 0xFF / 0 … 2550µA
Res = 10µA
...
10
...
DB9.7
...
1
...
72
...
OFF
...
Operating Condition
0 = Device is in Normal Operation and is Active
1 = Device is in Mounting Position and OFF
...
...
DB9.6
...
1
...
73
...
SFC
...
Storage Fully Charged
1 = Fully Charged
...
...
DB9.5
...
1
...
74
...
...
RESERVED
...
...
DB9.4
...
1
...
75
...
REFC
...
Reference Run Completed
1 = Successfully Completed
...
...
DB9.3…9.2
...
2
...
76
...
...
RESERVED
...
...
DB9.1…9.0
...
2
...
78
...
UM
...
User Mode
As set by the last received Downlink (DB3.3…3.2)
...
...
0b00
...
Valve Position %
...
0b01
...
SP Flow Temperature °C
...
0b10
...
RESERVED
...
0b11
...
RESERVED
...
0b11
...
RESERVED
...
11
...
DB10.7…10.0
...
8
...
80
...
UV
...
User Value according to User Mode
As set by the last received Downlink (DB0.7…0.0)
VALVE %: 0x00 … 0x64 / 0 … 100%
Res = 1%
FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C
Res = 0,5°C
...
Include Page | ||||
---|---|---|---|---|
|