BYTE | BIT RANGE | SIZE | OFFSET |
ABBREVIATION | DETAILS | ||||||
1 | DB0.7…0.0 | 8 | 0 | SPV | Set Point Value according to User Mode VALVE %: 0x00 … 0x64 / 0 … 100% Res = 1% FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C 0x00 = Default = 0x6E = 55°C Res = 0,5°C | ||
2 | DB1.7…1.0 | 8 | 8 |
| RESERVED Set to 0x00 | ||
3 | DB2.7…2.0 | 8 | 16 | SSV | Set Safety Value according to safety mode FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C 0x00 = Default = 0x6E = 55°C Res = 0,5°C VALVE %: 0x00 … 0x64 / 0 … 100% Res = 1% | ||
4 | DB3.7 | 1 | 24 |
| RESERVED | ||
| DB3.6…3.4 | 3 | 25 | RCI | Radio Communication Interval 0b010 = Default = 60 minutes | ||
0b000 | 10 minutes | ||||||
0b001 | 5 minutes | ||||||
0b010 | 60 minutes | ||||||
0b011 | 120 minutes | ||||||
0b100 | 480 minutes | ||||||
0b1zz | RESERVED | ||||||
| DB3.3…3.2 | 2 | 28 | UM | User Mode 0b01 = Default = SP Flow Temperature | ||
0b00 | Valve Position % | ||||||
0b01 | SP Flow Temperature °C | ||||||
0b10 | RESERVED | ||||||
0b11 | RESERVED | ||||||
| DB3.1…3.0 | 2 | 30 | SM | Safety Mode 0b01 = Default = SP Flow Temperature | ||
0b00 | RESERVED | ||||||
0b01 | SP Flow Temperature °C | ||||||
0b10 | Valve Position % | ||||||
0b11 | RESERVED | ||||||
5 | DB4.7…4.0 | 8 | 32 | RESERVED | |||
6 | DB5.7 | 1 | 40 | REF | Do Reference Run now Default = 0 | ||
| DB5.6…5. |
0b00
3
0b01
4
0b10
1
0b11
2
DB5.4…5.0
5
43
0 |
2
41
GAIN
Proportional Controller Gain
0b10 = Default = 1
7 | 41 | RESERVED |