BYTE | BIT RANGE | SIZE | OFFSET | ABBREV. | DETAILS | ||||
1 | DB0.7…0.0 | 8 | 0 | CVP | Current Valve Position % 0x00 … 0x64 / 0 … 100% Res = 1% | ||||
2 | DB1.7…1.0 | 8 | 8 | FSRV | Flow Sensor RAW Value °C 0x00 … 0xFF / 0 … 127.5°C Res = 0.5°C | ||||
3 | DB2.7…2.0 | 8 | 16 | FTMP | Flow TEMPERATURE Value °C
0x00 … 0xFF / 0 … 127.5°C Res = 0.5°C | ||||
4 | DB3.7…3.0 | 8 | 24 | ASRV | Ambient Sensor RAW Value °C 0x00 … 0xFF / 0 … 63.75°C Res = 0.25°C | ||||
5 | DB4.7…4.0 | 8 | 32 | ATMP | Ambient TEMPERATURE Value °C
0x00 … 0xFF / 0 … 63.75°C Res = 0.25°C | ||||
6 | DB5.7 | 1 | 40 |
| RESERVED | ||||
| DB5.6 | 1 | 41 | ES | Energy Storage is low 1 = Battery is low | ||||
| DB5.5 | 1 | 42 | HA | Harvesting 1 = Harvesting is active | ||||
| DB5.4 | 1 | 43 | ASF | Ambient Sensor Failure 1 = Sensor Failure | ||||
| DB5.3 | 1 | 44 | FSF | Flow Sensor Failure 1 = Sensor Failure | ||||
| DB5.2 | 1 | 45 | RCE | Radio Communication Error 1 = Radio Loss
| ||||
| DB5.1 | 1 | 46 | RSS | Radio Signal Strength 0 = Normal Radio Signal (RSSI is greater than -100 dBm) 1 = Weak Radio Signal (RSSI is less than -100 dBm) | ||||
| DB5.0 | 1 | 47 | ME | Motor 1 = Motor Error | ||||
7 | DB6.7…6.0 | 8 | 48 | STV | Storage Voltage V 0x00 … 0xFF / 0 … 5100mV Res = 20mV | ||||
8 | DB7.7…7.0 | 8 | 56 | ACC | Average Current Consumed 0x00 … 0xFF / 0 … 2550µA Res = 10µA | ||||
9 | DB8.7…7.0 | 8 | 64 | ACG | Average Current Generated
0x00 … 0xFF / 0 … 2550µA Res = 10µA | ||||
10 | DB9.7 | 1 | 72 | OFF | Operating Condition 0 = Device is in Normal Operation and is Active 1 = Device is in Mounting Position and OFF | ||||
| DB9.6 | 1 | 73 | SFC | Storage Fully Charged 1 = Fully Charged | ||||
| DB9.5 | 1 | 74 |
| RESERVED | ||||
| DB9.4 | 1 | 75 | REFC | Reference Run Completed 1 = Successfully Completed | ||||
| DB9.3…9. |
0 |
4 | 76 |
| RESERVED |
DB9.1…9.0
2
78
UM
User Mode
As set by the last received Downlink (DB3.3…3.2)
0b00
Valve Position %
0b01
SP Flow Temperature °C
0b10
RESERVED
0b11
RESERVED
0b11
RESERVED
11
DB10.7…10.0
8
80
UV
User Value according to User Mode
As set by the last received Downlink (DB0.7…0.0)
VALVE %: 0x00 … 0x64 / 0 … 100%
Res = 1%
FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C
Res = 0.5°C
Orah footnotes display |
---|