Acknowledgement of configuration
BYTE | BIT RANGE | SIZE | OFFSET | ABBREVIATION | DETAILS | |
1 | DB0.7 | 1 | 0 | ON | Devices will stay on regardless of 6-week Reference Run results 0 = If a 6-week Reference Run fails, device will switch off 1 = Device will stay on regardless of 6-week Reference Run results | |
DB0.6 | 1 | 1 | REC | Recalibration was Done 1 = The previous Downlink was an FPORT 0x0F Downlink instructing a Recalibration. Between the previous Downlink and this Uplink, a Recalibration was performed. Recalibration result is displayed in FPORT 0x01 Uplink bit CAL. | ||
DB0.5…0.1 | 5 | 2 | RESERVED | |||
DB0.0 | 1 | 7 | OFF | RESERVED OFF response will be displayed in FPORT 0x01 Uplink bit OFF |
...
. |
...
0 = Failed to Calibrate, 0% may be incorrect
...
Activity | Mounted behaviour | Unmounted behaviour |
Device Activation or Reset (magnet tap or magnet long hold) | Port 1 CAL bit 1 & OFF bit 0 Uplinks sent at 10 second intervals | Port 1 CAL bit 0 & OFF bit 1 No further Uplinks Long beep Device switches off |
Device goes to 0% but does not find an endstop | Port 1 CAL bit 0 & OFF bit 0 until next successful Recalibration (6-weekly or Downlink) | |
Port 8 Existing configuration to prevent switch-off 6-week recalibration | Port 1 CAL bit 0 & OFF bit 0 Port 1 CAL bit 1 & OFF bit 0 | Port 1 CAL bit 0 & OFF bit 0 until next successful Recalibration (6-weekly or Downlink) |
Port 1 Downlink Reference Run | Reference Run performed Port 1 CAL bit 1 & OFF bit 0 | Reference Run performed Port 1 CAL bit 0 & OFF bit 1 No further Uplinks Long beep Device switches off |
Port 0x0F Downlink Recalibration | Recalibration performed Port 0x0F acknowledgement Port 1 CAL bit 1 & OFF bit 0 | Recalibration performed Port 0x0F acknowledgement Port 1 CAL bit 0 & OFF bit 0 |
Port 0x0F Downlink OFF | Port 1 CAL bit 1 & OFF bit 1 Device switches off |
...