DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7

1

0

ON

Devices will stay on regardless of 6-week Reference Run results

0 = If a 6-week Reference Run fails, device will switch off

1 = Device will stay on regardless of 6-week Reference Run results

DB0.6

1

1

REC

Do a Recalibration Now

1 = Do a Recalibration Now

Regardless of whether device is mounted or unmounted, after a Recalibration the device will continue operating

DB0.5…0.1

5

2

RESERVED

DB0.0

1

7

OFF

Switch OFF the device

1 = Device will move to mounting position and switch OFF

DB0.7 setting will be stored in Non-Volatile Memory:

  • Devices which are instructed to stay on regardless of 6-week Reference Runs will retain this instruction, even when reset with a 5-second magnet hold

  • Devices which have never received a Port 8 instruction (eg newly produced devices) and which fail a 6-week Reference Run will switch off

UPLINK

Acknowledgement of configuration

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7

1

0

ON

Devices will stay on regardless of 6-week Reference Run results

0 = If a 6-week Reference Run fails, device will switch off

1 = Device will stay on regardless of 6-week Reference Run results

DB0.6

1

1

REC

Recalibration was Done

1 = The previous Downlink was an FPORT 0x0F Downlink instructing a Recalibration. Between the previous Downlink and this Uplink, a Recalibration was performed.

Recalibration result is displayed in FPORT 0x01 Uplink bit CAL.

DB0.5…0.1

5

2

RESERVED

DB0.0

1

7

RESERVED

OFF response will be displayed in FPORT 0x01 Uplink bit OFF.

Port 1 Bit 9.4 “REFC” will be renamed to “CAL”:

0 = Failed to Calibrate, 0% may be incorrect

1 = Successful Calibration

Activity

Mounted behaviour

Unmounted behaviour

Device Activation or Reset

(magnet tap or magnet long hold)

Port 1 CAL bit 1 & OFF bit 0

Uplinks sent at 10 second intervals

Port 1 CAL bit 0 & OFF bit 1

No further Uplinks

Long beep

Device switches off

Device goes to 0% but does not find an endstop

Port 1 CAL bit 0 & OFF bit 0

until next successful Recalibration (6-weekly or Downlink)

Port 8 Existing configuration to prevent switch-off

6-week recalibration

Port 1 CAL bit 0 & OFF bit 0

Port 1 CAL bit 1 & OFF bit 0

Port 1 CAL bit 0 & OFF bit 0

until next successful Recalibration (6-weekly or Downlink)

Port 1 Downlink Reference Run

Reference Run performed

Port 1 CAL bit 1 & OFF bit 0

Reference Run performed

Port 1 CAL bit 0 & OFF bit 1

No further Uplinks

Long beep

Device switches off

Port 0x0F Downlink Recalibration

Recalibration performed

Port 0x0F acknowledgement

Port 1 CAL bit 1 & OFF bit 0

Recalibration performed

Port 0x0F acknowledgement

Port 1 CAL bit 0 & OFF bit 0

Port 0x0F Downlink OFF

Port 1 CAL bit 1 & OFF bit 1

Device switches off