Comment: REV2.6

...

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.5

3

0

RESERVED

DB0.4

1

3

OPR

Opening Point Reset

1 = Reset Opening Point:

Device will set Opening Point Percent to Not Found.

When it is appropriate for the device to do so, the device will re-find the Opening Point Percent.

DB0.3…0.2

2

4

HW

Hot Water Availability

0b00

Use time of year to determine whether hot water is available

Orah footnote
textRequest day/time from gateway. OPD and SH only activate between 1st November to 28th February.
id4oa3m0v373r

0b01

Hot water is off

Orah footnote
textAfter 28 days from the last time the flag was set, the device will switch back to using the time of year to determine whether hot water is available.

0b10

Hot water is on

Orah footnote
textAfter 28 days from the last time the flag was set, the device will switch back to using the time of year to determine whether hot water is available.

0b11

RESERVED

DB0.1…0.0

2

6

SH

Slow Harvesting

Default = 0b11

0b00

Default Opening Point Detection and Slow Harvesting

Orah footnote
textActivation after 8 days of device continuously at 0%

0b01

Do Opening Point Detection and Slow Harvesting now

Orah footnote
textOpening Point Detection and Slow Harvesting will activate until next User Mode and User Value instructing a valve position ≠ 0%

0b10

Do Opening Point Detection now

Orah footnote
textOpening Point Detection will activate until next User Mode and User Value instructing a valve position ≠ 0%
id4cc7m1im6i7

Disable Slow Harvesting

0b11

Disable Opening Point Detection

Disable Slow Harvesting

2

DB1.7

1

8

RESERVED

DB1.6…1.0

7

9

MAX

Maximum Flow Sensor Raw Temperature °C

0x00 … 0x42 / 0 … 33°C

0x00 = Default = 0x34 = 26°C

Res = 0.5°C

...