BYTE | BIT RANGE | SIZE | OFFSET | ABBREVIATION | DETAILS | ||
1 | DB0.7…0.5 | 3 | 0 | RESERVED | |||
DB0.4 | 1 | 3 | OPR | Opening Point Reset 1 = Reset Opening Point: Device will set Opening Point Percent to Not Found. When it is appropriate for the device to do so, the device will re-find the Opening Point Percent. | |||
DB0.3…0.2 | 2 | 4 | HW | Hot Water Availability | |||
0b00 | Use time of year to determine whether hot water is available
| ||||||
0b01 | Hot water is off
| ||||||
0b10 | Hot water is on
| ||||||
0b11 | RESERVED | ||||||
DB0.1…0.0 | 2 | 6 | SH | Slow Harvesting Default = 0b11 | |||
0b00 | Default Opening Point Detection and Slow Harvesting
| ||||||
0b01 | Do Opening Point Detection and Slow Harvesting now
| ||||||
0b10 | Do Opening Point Detection now
Disable Slow Harvesting | ||||||
0b11 | Disable Opening Point Detection Disable Slow Harvesting | ||||||
2 | DB1.7 | 1 | 8 | RESERVED | |||
DB1.6…1.0 | 7 | 9 | MAX | Maximum Flow Sensor Raw Temperature °C 0x00 … 0x42 / 0 … 33°C 0x00 = Default = 0x34 = 26°C Res = 0.5°C |
...