BYTE | BIT RANGE | SIZE | OFFSET | ABBREVIATION | DETAILS | |||||||||
1 | DB0.7…0.0 | 8 | 0 | CVP | Current Valve Position % 0x00 … 0x64 / 0 … 100% Res = 1% | |||||||||
2 | DB1.7…1.0 | 8 | 8 | FTMP | Flow Temperature °C 0x00 … 0xFF / 0 … 127.5°C Res = 0.5°C | |||||||||
3 | DB2.7…2.0 | 8 | 16 | FMA | Flow Moving Average °C over the last 60 minutes 0x00 … 0xFF / 0 … 127.5°C Res = 0.5°C | |||||||||
4 | DB3.7…3.0 | 8 | 24 | ASRV | Ambient Sensor RAW Value °C 0x00 … 0xFF / 0 … 63.75°C Res = 0.25°C | |||||||||
5 | DB4.7…4.0 | 8 | 32 | ATMP | Ambient TEMPERATURE Value °C
0x00 … 0xFF / 0 … 63.75°C Res = 0.25°C | |||||||||
6 | DB5.7 | 1 | 40 |
| RESERVED | |||||||||
| DB5.6 | 1 | 41 | ES | Energy Storage is low 1 = Battery is low | |||||||||
| DB5.5 | 1 | 42 | HA | Harvesting 1 = Harvesting is active | |||||||||
| DB5.4 | 1 | 43 | ASF | Ambient Sensor Failure 1 = Sensor Failure | |||||||||
| DB5.3 | 1 | 44 | FSF | Flow Sensor Failure 1 = Sensor Failure | |||||||||
| DB5.2 | 1 | 45 | RCE | Radio Communication Error 1 = Radio Loss
| |||||||||
| DB5.1 | 1 | 46 | RSS | Radio Signal Strength 0 = Normal Radio Signal (RSSI is greater than -100 dBm) 1 = Weak Radio Signal (RSSI is less than -100 dBm) | |||||||||
| DB5.0 | 1 | 47 | ME | Motor 1 = Motor Error | |||||||||
7 | DB6.7…6.0 | 8 | 48 | STV | Storage Voltage V 0x00 … 0xFF / 0 … 5100mV Res = 20mV | |||||||||
8 | DB7.7…7.0 | 8 | 56 | ACC | Average Current Consumed 0x00 … 0xFF / 0 … 2550µA Res = 10µA | |||||||||
9 | DB8.7…7.0 | 8 | 64 | ACG | Average Current Generated
0x00 … 0xFF / 0 … 2550µA Res = 10µA | |||||||||
10 | DB9.7 | 1 | 72 | OFF | Operating Condition 0 = Device is in Normal Operation and is Active 1 = Device is in Mounting Position and OFF | |||||||||
| DB9.6 | 1 | 73 | SFC | Storage Fully Charged 1 = Fully Charged | |||||||||
| DB9.5 | 1 | 74 |
| RESERVED | |||||||||
| DB9.4 | 1 | 75 | CAL | Calibration OK
0 = Device is Unmounted 1 = Most recent Reference Run or Calibration was Successfully completed | |||||||||
| DB9.3…9.232 | 1 | 76 |
| RESERVED | |||||||||
| DB9. | 1…92…9.0 | 23 | 7877 | UM | User Mode As set by the last received Downlink (DB3.3…3.2) | ||||||||
| 0b000b000 | Valve Position % | ||||||||||||
0b001 | SP Flow Temperature °C | |||||||||||||
0b010 | RESERVED | |||||||||||||
0b011 | RESERVED | |||||||||||||
0b100 | RESERVED | 0b11|||||||||||||
0b101 | RESERVED | |||||||||||||
0b110 | Freeze Protect is active | |||||||||||||
0b111 | Forced Heating is active | |||||||||||||
11 | DB10.7…10.0 | 8 | 80 | UV | User Value according to User Mode As set by the last received Downlink (DB0.7…0.0) VALVE %: 0x00 … 0x64 / 0 … 100% Res = 1% FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C Res = 0.5°C
If Freeze Protect or Forced Heating is active, this value is the valve percent instructed by the device. |
Orah footnotes display |
---|