Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Comment: Fix column formatting
 

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.0

8

0

SPV

Set Point Value according to User Mode

VALVE %: 0x00 … 0x64 / 0 … 100%

Res = 1%

AMB TEMP: 0x00 … 0x50 / 0 … 40°C

0x00 = Default = 0x26 = 19°C

Res = 0.5°C

2

DB1.7…1.0

8

8

 RT

Room Temperature from RCU °C

0x00 … 0xA0 / 0 … 40°C

0x00 = No Room Temperature provided

Res = 0.25°C

3

DB2.7…2.0

8

16

SSV

Set Safety Value according to safety mode

AMB TEMP: 0x00 … 0x50 / 0 … 40°C

0x00 = Default = 0x26 = 19°C

Res = 0.5°C

VALVE %: 0x00 … 0x64 / 0 … 100%

Res = 1%

4

DB3.7

1

24


RESERVED

 

DB3.6…3.4

3

25

RCI

Radio Communication Interval

0b000 = Default = 10 minutes

0b000

10 minutes

0b001

5 minutes

0b010

60 minutes

0b011

120 minutes

0b100

480 minutes

0b101

RESERVED

0b110

RESERVED

0b111

RESERVED

 

DB3.3…3.2

2

28

UM

User Mode

0b10 = Default = SP Ambient Temperature

0b00

Valve Position %

0b01

RESERVED

0b10

SP Ambient Temperature °C

0b11

RESERVED

DB3.1…3.0

2

30

SM

Safety Mode

0b00 = Default = SP Ambient Temperature

0b00

SP Ambient Temperature °C

0b01

RESERVED

0b10

Valve Position %

0b11

RESERVED

DB4.7…4.0

8

32

RESERVED

6

DB5.7

1

40

REF

Do Reference Run now

Default = 0

1 = Reference Run now

DB5.6…5.0

7

41

RESERVED