Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Integral Unwind

If device reaches 0% and room is still too warm, or if device reaches 100% and room is still too cold:

0 = set

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.0

8

0

KP

P Coefficient

0 … 25.5255

Default = 0x18 0x14 = 2.420

Resolution = 0. 1

2

DB1.7…1.0

8

8

KI

I Coefficient

0 … 5.12

Default = 0x03 0x4B = 01.065

Resolution = 0.02

3

DB2.7…2.0

8

16

KD

D Coefficient

0 … 51.2

Default = 0x6F 0x00 = 22.20

Resolution = 0.2

4

DB3.7…3.10

78

24

RESERVED

DB3.0

1

31

IU

Unit
body--uriencoded--\int _%7B0%7D%5e%7Bt%7De(\tau )\,\mathrm %7Bd%7D \tau = 0

1 = set Unitbody--uriencoded--\int _%7B0%7D%5e%7Bt%7De(\tau )\,\mathrm %7Bd%7D \tau = \frac%7B-K_%7B\text%7Bp%7D%7D * e(t)%7D%7BK_%7B\text%7Bi%7D%7D%7D

Default = 0

5

DB4.7…4.0

8

32

CP

Closed Percent

Minimum percent that device will close to

Default = 0%

6

DB5.7…5.0

8

40

KD0

D Coefficient when closed

0 … 51.2

Default = 0x00 = 0.0

Resolution = 0.2

7

DB6.7…6.0

8

40

OFP

Offset Percent

Percentage Offset to be added to PID Output

Default = 0x00 = 0%

To receive an Uplink without changing any settings, send an empty Downlink.

...