// Decode uplink function.
//
// Input is an object with the following fields:
// - bytes = Byte array containing the uplink payload, e.g. [255, 230, 255, 0]
// - fPort = Uplink fPort.
// - variables = Object containing the configured device variables.
//
// Output must be an object with the following fields:
// - output = Object representing the decoded payload.
function decodeUplink(input) {
return {
data: Decode(input.fPort, input.bytes, input.variables)
};
}
function decode_port_1(input) {
var output = {
Current_Valve_Position: input[0],
Flow_Sensor_Raw: input[1] * 0.5,
Flow_Temperature: input[2] * 0.5,
Ambient_Sensor_Raw: input[3] * 0.25,
Ambient_Temperature: input[4] * 0.25,
Temperature_Drop_Detection: input[5]>>7 >> 7 & 0x01,
Energy_Storage: input[5]>>6 >> 6 & 0x01,
Harvesting_Active: input[5]>>5 >> 5 & 0x01,
Ambient_Sensor_Failure: input[5]>>4 >> 4 & 0x01,
Flow_Sensor_Failure: input[5]>>3 >> 3 & 0x01,
Radio_Communication_Error: input[5]>>2 >> 2 & 0x01,
Received_Signal_Strength: input[5]>>1 >> 1 & 0x01,
Motor_Error: input[5]>>0 >> 0 & 0x01,
Storage_Voltage: Number((input[6] * 0.02).toFixed(2)),
Average_Current_Consumed: input[7] * 10,
Average_Current_Generated: input[8] * 10,
Operating_Condition: input[9]>>7 >> 7 & 0x01,
Storage_Fully_Charged: input[9]>>6 >> 6 & 0x01,
Zero_Error: input[9]>>5 >> 5 & 0x01,
Calibration_OK: input[9]>>4 >> 4 & 0x01,
}
var um = input[9] & 0x07;
var uv = (um === 0) ? input[10] : input[10] * 0.5;
output.User_Mode = um;
output.User_Value = uv;
if (input.length == 12) {
utmp = input[11] * 0.25;
output.Used_Temperature = utmp;
}
return output ;
}
function Decode(fPort, bytes) {
var output = {};
switch (fPort) {
case 1:
output = decode_port_1(bytes);
break;
default:
return {
errors: ['unknown FPort'],
};
}
return output;
}
|