Code Block | ||
---|---|---|
| ||
// Encode downlink function.
//
// Input is an object with the following fields:
// - output = Object representing the payload that must be encoded.
// - variables = Object containing the configured device variables.
//
// Output must be an object with the following fields:
// - bytes = Byte array containing the downlink payload.
// Possible Options:
// userMode : "Ambient_Temperature" or "Valve_Position"
// setValue : 0 to 40 (0.5° resolution) for "Ambient_Temperature"
// setValue : 0 to 100 (1% resolution) for "Valve_Position"
// safetyMode : "Ambient_Temperature" or "Valve_Position"
// safetyValue : 0 to 40 (0.5° resolution) for "Ambient_Temperature"
// safetyValue : 0 to 100 (1% resolution) for "Valve_Position"
// roomTemperature : 0 (Internal Ambient Estimate) or Temperature from External Sensor (0.25° resolution)
// radioInterval : 5 or 10 or 60 or 120 or 480 (minutes)
// doReferenceRunNow : 0 or 1 (0-False; 1-True)
function encodeDownlink(input) {
let mode = input.data.userMode; // "Ambient_Temperature" or "Valve_Position"
let safetyMode = input.data.safetyMode; // "Ambient_Temperature" or "Valve_Position"
let setValue = input.data.setValue; // 0-40 for Ambient_Temperature, 0-100 for Valve_Position
let roomTemperature = input.data.roomTemperature; // 0-40
let safetyValue = input.data.safetyValue; // 0-40 for Ambient_Temperature, 0-100 for Valve_Position
let radioInterval = input.data.radioInterval; // 5, 10, 60, 120, 480
let doReferenceRunNow = input.data.doReferenceRunNow; // 0 or 1
let bytes = [0, 0, 0, 0, 0, 0];
// Byte 1: Set value
if (mode === "Ambient_Temperature") {
if (setValue < 0 || setValue > 40) {
throw new Error("Set value out of range for ambient mode");
}
else {
bytes[0] = setValue *2;
}
} else if (mode === "Valve_Position") {
if (setValue < 0 || setValue > 100) {
throw new Error("Set value out of range for valve mode");
}
else {
bytes[0] = setValue;
}
} else {
throw new Error("Invalid user mode");
}
// Byte 2: Room temperature (0-40)
if (roomTemperature < 0 || roomTemperature > 40) {
throw new Error("Room temperature out of range");
}
else {
bytes[1] = roomTemperature * 4;
}
// Byte 3: Safety value
if (safetyMode === "Ambient_Temperature") {
if (safetyValue < 0 || safetyValue > 40) {
throw new Error("Safety value out of range for ambient mode");
}
else {
bytes[2] = safetyValue * 2;
}
} else if (safetyMode === "Valve_Position") {
if (safetyValue < 0 || safetyValue > 100) {
throw new Error("Safety value out of range for valve mode");
}
else {
bytes[2] = safetyValue;
}
} else {
throw new Error("Invalid safety mode");
}
// Byte 4: Radio interval, user mode, safety mode
let radioBits;
switch (radioInterval) {
case 5:
radioBits = 1 << 4; // Radio interval 5 minutes
break;
case 10:
radioBits = 0 << 4; // Radio interval 10 minutes
break;
case 60:
radioBits = 2 << 4; // Radio interval 60 minutes
break;
case 120:
radioBits = 3 << 4; // Radio interval 120 minutes
break;
case 480:
radioBits = 4 << 4; // Radio interval 480 minutes
break;
default:
throw new Error("Invalid radio interval");
}
let userModeBits;
if (mode === "Ambient_Temperature") {
userModeBits = 2 << 2; // User mode "Ambient_Temperature" in bits 3 and 4
} else {
userModeBits = 0 << 2; // User mode "Valve_Position" in bits 3 and 4
}
let safetyModeBits;
if (safetyMode === "Ambient_Temperature") {
safetyModeBits = 0 << 0; // Safety mode "Ambient_Temperature" in bits 1 and 2
} else {
safetyModeBits = 2 << 0; // Safety mode "Valve_Position" in bits 1 and 2
}
bytes[3] = radioBits | userModeBits | safetyModeBits;
// Byte 5: Reserved (set to 0)
bytes[4] = 0;
// Byte 6: doReferenceRunNow bit (bit 8)
if (doReferenceRunNow < 0 || doReferenceRunNow > 1) throw new Error("Invalid doReferenceRunNow value");
bytes[5] = doReferenceRunNow << 7;
return {
"bytes": bytes
};
} |
...
Code Block | ||
---|---|---|
| ||
// Example 1 { "userMode": "Valve_Position", "setValue": 42, "roomTemperature": 0, "safetyMode": "Ambient_Temperature", "safetyValue": 19, "radioInterval": 5, "doReferenceRunNow": 1 } // Example 2 { "userMode": "Ambient_Temperature", "setValue": 21.5, "roomTemperature": 24, "safetyMode": "Valve_Position", "safetyValue": 0, "radioInterval": 60, "doReferenceRunNow": 0 } // Example 3 { "userMode": "Valve_Position", "setValue": 36, "roomTemperature": 0, "safetyMode": "Valve_Position", "safetyValue": 21, "radioInterval": 5, "doReferenceRunNow": 1 } // Example 4 { "userMode": "Ambient_Temperature", "setValue": 20.5, "roomTemperature": 023.75, "safetyMode": "Ambient_Temperature", "safetyValue": 18, "radioInterval": 10, "doReferenceRunNow": 0 } |