The unit has no user-accessible buttons to avoid manipulation of the device in public environments. Installers rely on a pen-shaped magnet to perform tasks related to the installation.

...

In a web browser, navigate to the gateway IP address

  1. Login to the gateway

  2. LoRaWAN, Network Settings, Join Delay 5 seconds

  3. LoRaWan, Network Settings, Max Datarate 5 – SF7BW125
    Click Submit
    Wait for Save and Apply to go red, and then click it

  4. Firewall, Settings, Input Filter Rules
    Add ‘Allow Inbound’

  5. Click Submit

  6. Wait for Save and Apply to go red, and then click it

Pairing the Device with a Room Controller or Gateway

...

To pair a device to a MultiTech gateway:

  1. In a web browser, navigate to the gateway IP address

  2. Login to the gateway

  3. LoRaWAN, Key Management, click Add New

  4. For each device, enter the following details, and then click OK:
    Dev EUI (available in the spreadsheet)
    App EUI (available in the spreadsheet)
    App Key (available in the spreadsheet)
    Class: A
    Device Profile: LW102-OTA-EU868
    Network Profile: DEFAULT-CLASS-A

  5. Click Submit

  6. Wait for Save and Apply to go red, and then click it

Mounting Position and OFF

...

Once the unit is securely attached to the valve,

  1. Briefly tap the pen magnet on the micr°pelt logo on the product’s cover

  2. The radio establishes a link to the gateway

    Unit
    body\rightarrow
    upon successful completion, a double-beep sounds

  3. The motor performs a reference run

    Unit
    body\rightarrow
    upon successful completion, a triple-beep sounds

  4. The unit is now active

Activation only works from mounting position. If performed during normal operation, the product will not show any reaction.

...

The RESET function allows access to mounting position. It is also useful to restore correct operation should a malfunction occur.

To RESET the device,

  1. Hold the pen magnet to the micr°pelt logo on the product’s cover until a beep sounds

  2. The internal microcontroller will reset and restart

If the device is mounted on a valve, it will activate

...