An offset occurs between the flow temperature sensor installed in the MLR003 and the actual temperature in the water circuit. (This offset is due to thermal transitions: a temperature drop in the valve itself, and via the valve connection/adapter to the MLR003 sensor.) This offset is compensated by the automatic offset correction function in the MLR003.
Therefore, the device uses the following automatic offset correction:
Mathblock | ||||
---|---|---|---|---|
| ||||
--uriencoded--\text%7BFlow Temperature%7D = 0.0023 * \text%7BSensor Value%7D%5e2 + 1.0499 * \text%7BSensor Value%7D - 1.3292 |