You find the quick-start guide here: MVA008 Quickstart Guide
Installation with Manual Pairing
No | Objective | Button No. | Action | LED Activity | Reasons for failure |
1 | Pairing from mounting position (= shipping condition = OFF) or normal operation (while buttons not locked) | Turn dial to end position Left OR Right and hold 5 seconds until 1x green or 3x red LED | Unit does pair and remains in mounting position = shipping condition = OFF If unit is not in mounting position, it moves to mounting position now. | Success: Single green flash Failure: Triple red flash | Controller or gateway either not present or not in pairing mode, so that pairing fails |
2 | Mounting
|
| Mount the actuator before executing run-in sequence and normal operation |
|
|
3 | Run-in sequence and normal operation from mounting position | Turn to end position Left OR Right for short press (< 1 second) | Unit executes run-in sequence; radio communication occurs every 10 seconds for 10 minutes, and then reverts to every 10 minutes. One hour after this action, the pushbutton switches will lock and can only be unlocked, by performing RESET (5.) | Success: Single green flash Failure: Triple red flash | Motor or gear error |
4 | Get new target value (while buttons not locked) | Turn to end position Left OR Right for short press (< 1 second) | Unit immediately gets target value from controller / gateway, then moves to the new target | Success: Single green flash Failure: Triple red flash | Unit cannot contact the controller or gateway |
5 | Return to mounting position | Turn dial to end position Left OR Right and hold 5 seconds until single green flash | Green LED appears, followed a triple red LED. The device will turn the motor back to mounting position and switch off. | Success: Single green flash followed by triple red flash
| |
6 | Deactivate button lock and RESET followed by normal operation | Pull the dial straight off and press both buttons simultaneously for 10 seconds. | The unit enters normal operation, assuming it is paired. For 60 min, the unit will accept a 5-second long-press of any button and for 10 minutes, it will run at a 10-second radio communication interval. It contacts the controller / gateway immediately after RESET. | After 10 seconds 1x green (RESET activated), then 2x red (new start), after a short break 1x green (normal operation with successful communication) or 3x red (communication error, mounting error) | Unit cannot contact the controller or gateway it has been paired with or unit has never been paired. Mounting or motor problems |