EnOcean Link Table

MVA008 supports the following number of tech-in relationships:

...

The P parameter describes the internal multiplier in the temperature control loop (only with SPS bit = 1) for calculating the valve adjustment % value. With setting 30, a valve opening of 19% is calculated for a temperature failure of 1°C (T ACTUAL = 21 ° C and T TARGET = 22 ° C). An internally determined ambient temperature value is used for the internal calculation of the controller when in automatic offset mode, which is why the corresponding valve opening angles are not calculated using the above method.

ReCom device parameter

INDEX

Description

Ambient to target temp offset [K]

0

(0x00) 0 … Auto* (DEFAULT)

(0x01) 1 … -3 K

(0x02) 2 … -2 K

(0x03) 3 … -1 K

(0x04) 4 … 0 K

(0x05) 5 … +1 K

(0x06) 6 … +2 K

(0x07) 7 … +3 K

(0x0F) 15 … +11 K

Radio communication interval [s/min]

1

(0x00) 0…Auto * (DEFAULT)

(0x01) 1 … 10sec (for debugging only)

(0x02) 2 … 2min

(0x03) 3 … 5min

(0x04) 4 … 10 min

(0x05) 5 … 20min

(0x06) 6 … 30min

* Automatic mode: 2/5/10 minutes interval based on flow temperature and internal storage

Execute Reference Run

10

0x01

DEFAULT 0x00

Auto ambient to target offset parameter

11

(0x00 … 0xFF) 0 … 255

MVA008 DEFAULT* 44 (0x2C)

  • Micropelt Internal parameter

Temp.-control loop gain parameter

12

(0x00 … 0xFF) 0 … 255 = 10x GAIN

DEFAULT 30 = 0x1E

Battery open circuit voltage (V)

13

READ ONLY

(0x00 … 0xFF) 0 … 255 = 10x Voltage

Example 0x21 = DEZ 33 : 10 = 3,3Volt

...