Parameter
...
Range
...
Valve thread
...
M 30 x 1,5 (adapter available for other types)
...
Ambient operating temperature
...
0 - 40°C, max 70% rH
...
Flow pipe temperature
...
75°C max
...
Transportation & storage temperature range
...
-10 - +45°C, max 70% rH
...
Max pin stroke (calibration range)
...
> 5 mm
...
Operating pin stroke (0-100 %)
...
2.0 mm typical
...
Pin Stroke Resolution (defined by EnOcean Equipment Profile A5-20-01)
...
Steps of 1%
...
Adjustment speed
...
0.95 mm/s typical
...
Stall force
...
100 N typical
...
Noise level
...
~ 30 dB(A)
...
RF communication interval
...
According to A5-20-06
...
RF communication interval
Activation / installation
...
2 Minutes
(Will revert to A5-20-06 settings after 30 minutes)
...
Ambient Temperature
Activation / installation
...
Effective Ambient sensor value
(Will revert to approximated value after 30 minutes. Calibration time in radiator closed situation 3 x 10 Minutes. Start value smoothing = 20°C); requires stable flow temperature when heating is on.
...
Freeze protection
...
Below 6ºC, open valve to 95%
Normal operation when T flow > 6°C
0°C when setpoint temperature = 0°C
...
Window open detection
...
Yes
...
Safe position
(following 6 consecutive communication failures)
...
Internal temperature controller with last valid setpoint °C, otherwise default value 21°C
Will revert to standard operation as soon as radio communication is online again
...
EnOcean EEP
...
A5-20-06
(Valve Position or Setpoint Temperature)
...
EnOcean Remote management & Remote commissioning
...
Yes (Section 9)
...
DDF (Device description file)
...
Yes
(Pls. contact Micropelt)
...
Life cycle status and monitoring capabilities
...
Yes
(Section 8)
...
Local offset control
...
+/- 5°C
(Section 4)
...
Accuracy of ambient and flow temperature sensor
...
+/- 0.5 ºC
...
Ambient temperature sensor offset compensation
...
Default: Automatic Offset compensation
(Configurable through Remote Commissioning)
...
Energy storage
...
Construed for full year operation and recharged. Immediately ready for use if stored for up to 12 months and at a storage temperature of no more than 40ºC
...
Energy generation minimum requirement
...
90 standard heating days per year with T flow >45°C
...
Battery voltage flag
...
Battery voltage < 3.1 V
(RF communication interval will be set to 10 minutes)
...
Radio carrier frequency
...
868.3 MHz
...
Maximum radiated power
...
+1.4 dBm (EN 300220-2:V3.1.1)
...
Receiver
...
Category 2 (EN 300 220-1 V3.1.1)
...
Conformity
...
CE
...