EnOcean Remote Management (ReMan), Remote Commissioning (ReCom)
Table of Contents |
---|
EnOcean Link Table
MVA005 supports the following number of tech-in relationships:
...
ReCom internal MVA Parameter
Pls. contact Micropelt for further details and device Device description file (DDF, xml) .can be found here Overview MVA EnOcean
Description INDEX 0 = Ambient to Target Offset [K]
...
The signal communication interval can be changed from its default value of 12 hours to carry out Remote commissioning operations with short(er) time intervals.
ReCom Device Parameter | INDEX | Description |
Ambient to Target Offset [K] | 0 | (0x00) 0 … Auto* (DEFAULT) (0x01) 1 … -3 K (0x02) 2 … -2 K (0x03) 3 … -1 (0x04) 4 … 0 K (0x05) 5 … +1 K (0x06) 6 … +2 K (0x07) 7 … +3 K … (0x0F) 15 … +11 K |
Radio communication interval [s/min] | 1 | (0x00) 0…Auto * (DEFAULT) (0x01) 1 … 10sec (For debug only) (0x02) 2 … 2min (0x03) 3 … 5min (0x04) 4 … 10 min (0x05) 5 … 20min (0x06) 6 … 30min
|
Buzzer | 6 | Without function, read-only
DEFAULT 0x00 |
Execute reference run | 10 | 0x01
DEFAULT 0x00 |
Ambient to Target Offset (A) Parameter | 11 | (0x00 … 0xFF) 0 … 255
MVA005 DEFAULT DEZ 56 = HEX 0x38 |
Temperature Control Gain „P“ Parameter
| 12 | (0x00 … 0xFF) 0 … 255
DEFAULT DEZ 90 = HEX 0x5A |
Internal storage voltage (V) | 13 NUR LESEN | (0x00 … 0xFF) 0 … 255
Example: HEX 0x21 = DEZ 33 : 10 = 3,3 Volt |
Signal communication cycle
NOTE: Setting of summer bit (8h 4BS communication cycle) does not change the SIGNAL telegram cycle.
| 14 | 0x00 … 1min 0x01 … 5min 0x02 … 10min 0x03 … 20min 0x04 … 60min 0x05 … 120min 0x06 … 240min 0x07 … 360min 0x08 … 720min 0x09 … 1440min
Default: 720min (12h) |
...