Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

 

...

Installation cycle

...

Standard

operation

...

Idle state

...

Radio failure

...

Forced heating

...

Freeze Protection

...

Comments

...

 

...

Valve target %

Or

Flow target temperature

 

...

Phases between monitoring and communicating

...

Transmit messages not received by the gateway

...

Valve opens to 50%

(or remains in current position if current position is >= 50%)

...

Valve opens to 95%

...

Trigger

...

Magnetic switch.

Join accept

from Gateway,

& Device is mounted

...

Internal timer

...

Internal timer

...

From activation:

No Gateway connect

from standard operation: 6 consecutive Gateway communication failures

...

Battery voltage < 2V

...

Flow sensor raw temperature

<= 6°C

...

Radio communication interval (RCI)

...

10 seconds for 5 minutes

...

5 minutes

10 minutes

60 minutes

120 minutes

480 minutes

...

OFF

...

Three times 30 seconds

Then once 2 minutes

Then 60 minutes

...

OFF

...

OFF

...

Dynamic change of communication interval

Orah footnote
textA change of the communication interval or operating mode is possible with every regular radio telegram

...

No

...

Yes

...

No

...

No

...

No

...

No

...

Sensors

(flow, ambient)

...

Active, every 10 seconds

...

Active

...

OFF

 

...

Active

...

OFF

...

Active, every

2 minutes

...

Freeze protection

...

Active, every 10 seconds

...

Active, every 150 seconds

...

OFF

...

Active, every 150 seconds

...

OFF

...

Active

...

Motor operation

...

Reference run.

Then active, according to Radio Communication

...

Active, according to

Radio Communication

...

OFF

...

Active

...

OFF

...

OFF

...

Monitoring of battery

...

Active, every 10 seconds

...

Active

...

OFF

...

Active

...

Active, every 12 hours

...

Active, every

2 minutes

...

Internal temperature controller

...

If User Mode is Set Point Flow Temperature: active

...

If User Mode is Set Point Flow Temperature: active

...

OFF

...

If Safety Mode is Set Point Flow Temperature: active

...

OFF

...

OFF

...

Default upon activation and no downlinks

...

Set Point Flow 57°C

Flow offset 5°C

...

Set Point Flow 57°C

Flow offset 5°C

...

Set Point Flow 57°C

Flow offset 5°C

...

Include Page
MLRD:MLR003R: Operating Modes
MLRD:MLR003R: Operating Modes