Transmit mode from MVA to controller/ gateway/ server

 

Receive mode from controller / gateway / server to MVA

DB3.7…DB3.0 (CV)

Current valve position 0...100%, linear n=0...100

 

DB3.7…DB3.0 (SP)

New valve position (0...100% ~ 0x00…0x64) or Target temperature (0…40°C ~ 0x00…0xFF)

 

Selection with SPS DB1.2

DB2.7

Not used

 

DB2.7…DB2.0 (TMP)

Room temperature from room sensor (0…40ºC ~ 0xFF…0x00*) for operation with the internal MVA ambient sensor must be set to 0x00

DB2.6 (ENIE)

Active energy harvesting (valve is hot)

 

DB1.7....DB1.4

Not used (set to “zero”)

DB2.5 (ES)

Energy storage sufficiently filledcharged

 

 

DB1.3 (SB)

Summer mode transmit / receive time interval 8 hours

DB2.4 (BCAP)

Storage capacity sufficient (analog DB_2. Bit_5)

 

DB1.2 (SPS)*1

Setpoint Selection
0: Valve pos. (0…100%)
1: Temp. setpoint (0…40°C)

DB2.3

Not used

 

DB1.1…DB1.0

Not used (set to “zero”)

DB2.2 (FTS)

Temperature sensor failure

 

DB0.7…DB0.4

Not used (set to “zero”)

DB2.1 (DWO)

Window open detection

 

DB0.3 (LRNB)

LRN Bit, defined for data telegram

DB2.0 (ACO)

Motor failure

 

DB0.2…DB0.0

Not used (set to “zero”)

DB1.7…DB1.0 (TMP)

Ambient temperature MVA

(0…40°C ~ 0x00…0xFF)

 

 

 

DB0.7…DB0.4

Not used

 

 

 

DB0.3 (LRNB)

LRN Bit, defined for data telegram

 

 

 

DB0.2…DB0.0

Not used

 

 

 

...

Actuator → Controller / Gateway

 

4 Byte:

32708908

 

 

 

HEX

BIN

DEC

DB3.7-0

32

00110010

50

CV = Current valve opening =  50 %

DB2.7-0

70

01110000

112

SO

DB2.7

0

0 = Normal operation

1 = Service on

ENIE

DB2.6

1

0 = no energy input

1 = Energy input enabled (Harvesting active)

ES

DB2.5

1

0 = Energy storage low

1 = Energy storage sufficiently charged

BCAP

DB2.4

1

0 = Battery low,
replace soon

1 = Battery OK

DB2.3

0

 

 

FTS

DB2.2

0

0 = Temp sensor OK

1 = Temp sensor out of range

DB2.1

0

 

 

ACO

DB2.0

0

0 = Actuator normal operation

1 = Actuator obstructed

DB1.7-0

89

10001001

137

TMP = Ambient temperature from actuator = 21.5 ºC

DB0.7-0

08

00001000

8

LRN Type

DB0.7

0

0 = not used [no EEP & Mfg ID)

1 = not used [with EEP & Mfg ID)

EEP Result

DB0.6

0

0 = not used [EEP not supported]

1 = not used [EEP supported]

LRN Result

DB0.5

0

0 = not used [Sender ID deleted]

1 = not used [Sender ID stored]

LRN Status

DB0.4

0

0 = not used [Teach-In query]

1 = not used [Teach-In response]

LRNB

DB0.3

1

0 = Teach-in Telegram

1 = Data Telegram

DB0.2

0

0 = not used

1 = not used

DB0.1

0

0 = not used

1 = not used

DB0.0

0

0 = not used

1 = not used

...