FPort Number
...
Type of operation
...
Payload length
...
Description
...
Commenst
...
0x00
...
MAC Commands
...
8 Bytes
...
RESERVED
...
0x01
...
Valve position % mode
Temperature setpoint mode (°C) with flow temperature sensor
...
Downlink:
6 Bytes
Uplink:
11 Bytes
...
Actuator operation mode with valve position % only
Self-regulation mode of the flow actual temperature, using the flow requested temperature
Default upon device activation with setpoint 57°C
...
0x02
...
Report REV Number, Hardware and Firmware Version
...
Downlink:
n Byte(s)
Uplink:
6 Bytes
...
Request REV Number, Hardware and Firmware Version from MLR003FiEU61-12-1.1
...
Only supported in radiator product series MLR003R.
...
0x03
...
Motor operating range
...
Downlink:
1 Byte
Uplink:
1 Byte
...
Set/change motor operating range (mm) from default value 2,56mm
...
Only supported in radiator product series MLR003R.
...
0x04
...
LoRa Spread Factor
...
Downlink:
1 Byte
Uplink:
1 Byte
...
Set/change LoRa spread factor from default value
...
Only supported in radiator product series MLR003R.
...
0x05
...
Slow Harvesting (SH) and Valve opening point detection OPD)
...
Downlink:
1 Byte
Uplink:
1 Byte
...
Activate and report OPD, activate/deactivate Slow Harvesting
...