BYTE | BIT RANGE | SIZE | OFFSET | ABBREVIATION | DETAILS | |||||||
1 | DB0.7…0.0 | 8 | 0 | SPV | Set Point Value according to User Mode VALVE %: 0x00 … 0x64 / 0 … 100% Res = 1% AMB TEMP: 0x00 … 0x50 / 0 … 40°C 0x00 = Default = 0x26 = 19°C Res = 0 | ,.5°C | ||||||
2 | DB1.7…1.0 | 8 | 8 | RT | Room | TMP Temperature from RCU °C 0x00 … 0xA0 / 0 … 40°C 0x00 = No Room | TMP Temperature provided Res = 0 | ,.25°C | ||||
3 | DB2.7…2.0 | 8 | 16 | SSV | Set Safety Value according to safety mode AMB TEMP: 0x00 … 0x50 / 0 … 40°C 0x00 = Default = 0x26 = 19°C Res = 0 | ,.5°C VALVE %: 0x00 … 0x64 / 0 … 100% Res = 1% | ||||||
4 | DB3.7 | 1 | 24 | RESERVED | ||||||||
| DB3.6…3.4 | 3 | 25 | RCI | Radio Communication Interval 0b000 = Default = 10 minutes | |||||||
0b000 | 10 minutes | |||||||||||
0b001 | 5 minutes | |||||||||||
0b010 | 60 minutes | |||||||||||
0b011 | 120 minutes | |||||||||||
0b100 | 480 minutes | |||||||||||
0b101 | RESERVED | |||||||||||
0b110 | RESERVED | |||||||||||
0b111 | RESERVED | |||||||||||
| DB3.3…3.2 | 2 | 28 | UM | User Mode 0b10 = Default = SP Ambient Temperature | |||||||
0b00 | Valve Position % | |||||||||||
0b01 | RESERVED | |||||||||||
0b10 | SP Ambient Temperature °C | |||||||||||
0b11 | RESERVED | |||||||||||
DB3.1…3.0 | 2 | 30 | SM | Safety Mode 0b00 = Default = SP Ambient Temperature | ||||||||
0b00 | SP Ambient Temperature °C | |||||||||||
0b01 | RESERVED | |||||||||||
0b10 | Valve Position % | |||||||||||
0b11 | RESERVED | |||||||||||
5 | DB4.7…4.0 | 8 | 32 | RESERVED | ||||||||
6 | DB5.7 | 1 | 40 | REF | Do Reference Run now Default = 0 1 = Reference Run now | |||||||
DB5.6…5.0 | 7 | 41 | RESERVED |