Comment: Empty Downlink

DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREV.

ABBREVIATION

DETAILS

1

DB0.7…0.5

3

0

RESERVED

DB0.4

1

3

OPR

Opening Point Reset

1 = Reset Opening Point:

Device will set Opening Point Percent to Not Found.

When it is appropriate for the device to do so, the device will re-find the Opening Point Percent.

DB0.3…0.2

2

4

HW

Hot Water Availability

0b00

Use time of year to determine whether hot water is available

Orah footnote
text

The device anticipates hot water to be available from

Request day/time from gateway. OPD and SH only activate between 1st November to 28th February

of each year.

.
id4oa3m0v373r

0b01

Hot water is off

Orah footnote
textAfter 28 days from the last time the flag was set, the device will switch back to using the time of year to determine whether hot water is available.

0b10

Hot water is on

Orah footnote
textAfter 28 days from the last time the flag was set, the device will switch back to using the time of year to determine whether hot water is available.

0b11

RESERVED

DB0.1…0.0

2

6

SH

Slow Harvesting

Default = 0b11

0b00

Default Opening Point Detection and Slow Harvesting

Orah footnote
textActivation after 8 days of device continuously at 0%

0b01

Do Opening Point Detection and Slow Harvesting now

Orah footnote
textOpening Point Detection and Slow Harvesting will activate until next User Mode and User Value instructing a valve position ≠ 0%

0b10

Do Opening Point Detection now

Orah footnote
textOpening Point Detection will activate until next User Mode and User Value instructing a valve position ≠ 0%
id4cc7m1im6i7

Disable Slow Harvesting

0b11

Disable Opening Point Detection

Disable Slow Harvesting

2

DB1.7

1

8

 

RESERVED

DB1.6…1.0

7

9

MAX

Maximum Flow Sensor Raw Temperature °C

0x00 … 0x42 / 0 … 33°C

0x00 = Default = 0x34 = 26°C

Res = 0.5°C

Orah footnotes display

To receive an Uplink without changing any settings, send an empty Downlink.

UPLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREV.

ABBREVIATION

DETAILS

1

DB0.7

1

0

OPF

Opening Point Percent has been found

0

Not Found

1

Found

DB0.6…0.0

7

1

OP

Opening Point Percent

0x00 … 0x64 / 0 … 100%

Res = 1%

2

DB1.7…1.3

5

8

RESERVED

DB1.2…1.0

3

13

SH

Slow Harvesting Status

0b000

Not Slow Harvesting because Slow Harvesting is switched off in Downlink

0b001

Not Slow Harvesting because recently target % ≠ 0%

0b010

Not Slow Harvesting because hot water is expected to be off

0b011

Cannot detect Opening Point

0b100

Not Slow Harvesting because battery is high

0b101

Not Slow Harvesting because Slow Harvesting was attempted but generated insufficient current

0b110

Detecting Opening Point

0b111

Slow Harvesting