| Installation cycle | Standard operation | Idle state | Radio failure |
Comments |
| Ambient Temperature Measurement, Presence Detection and Set Point Functionality
| Phases between monitoring and communicating | Uplinks not received by the gateway |
Trigger |
When Battery is first connected (or) when the device is RESET using Push Button Join accept from Gateway | Internal timer | Internal timer | From activation: No Gateway connect From standard operation: 3 consecutive Gateway communication failures | |
Radio communication interval (RCI) | 10 seconds for 5 minutes | 5 minutes | OFF | Three times 30 seconds Then once 2 minutes Then 60 minutes |
Dynamic change of communication interval | No | No | No | No |
Sensors (Temperature, PIR) | Active, every 10 seconds | Active | Only PIR
| Active |
Monitoring of battery | Active, every 10 seconds | Active | OFF | Active |