Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Comment: REV2.a : Default

...

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7

1

0

MSET

Set the Motor Operating Range

1 = Set the Motor Operating Range

DB0.6…0.4

3

17…0.4

4

0

RESERVED

DB0.3…0.0

4

4

MVMOR

Motor Operating Range Value

Orah footnote
textResolution: The resolution increases with the reduced motor operating range = travel distance. E.g., 1.456mm/100% = 0.01456mm/1% valve position instead of default 2.56048mm/100%
idi7kqnp8d35a

0b0000

Default (2.56048mm)

0b0001

RESERVED

0b0010

RESERVED

0b0011RESERVED

0.624mm

0b0100RESERVED

0.832mm

0b0101RESERVED

1.040mm

0b0110RESERVED

1.248mm

0b0111

1.456mm

0b1000

1.664mm

0b1001

1.872mm (Default)

0b1010

2.080mm

0b1011

2.288mm

0b1100

2.496mm

0b1101

RESERVED

0b1110

RESERVED

0b1111

RESERVED

Orah footnotes display

Note: Sending an FPORT 0x03 Downlink will cause the device to respond with an FPORT 0x03 Uplink. Thus, to get Motor Operating Range details To receive an Uplink without changing any optionssettings, send an empty FPORT 0x03 Downlink, or an FPORT 0x03 Downlink with 0s.


UPLINK

...

BYTE

...

BIT RANGE

...

SIZE

...

OFFSET

...

ABBREVIATION

...

DETAILS

...

1

...

DB0.7…0.4

...

4

...

0

...

RESERVED

...

DB0.3…0.0

...

4

...

4

...

MV

...

Motor Operating Range Value

...

0b0000

...

Default (2.56048mm)

...

0b0001

...

RESERVED

...

0b0010

...

RESERVED

...

0b0011

...

RESERVED

...

0b0100

...

RESERVED

...

0b0101

...

RESERVED

...

0b0110

...

RESERVED

...

0b0111

...

1.456mm

...

0b1000

...

1.664mm

...

0b1001

...

1.872mm

...

0b1010

...

2.080mm

...

0b1011

...

2.288mm

...

0b1100

...

2.496mm

...

0b1101

...

RESERVED

...

0b1110

...

RESERVED

...

0b1111

...

Same as Downlink, confirming settings.