Parameter | Value | ||||
Ambient operating temperature range | 0 to 40°C, max 70% rH | ||||
Flow pipe temperature | 75°C max | ||||
Transportation & storage temperature range | -20 to +45°C, max 70% rH | ||||
Dimensions (LWH) | 83 x 60 x 64 mm (63 x 60 x 64 mm without valve connector) | ||||
Weight | 280 g (excluding packing) | ||||
Operation at high altitude | Max 2000 m / 6500 ft above sea level | ||||
Pin stroke (calibration range) | <= 5.5 mm | ||||
Operating pin stroke (0-100%) | 2.56 mm typical | ||||
Pin Stroke Resolution | Steps of 1% | ||||
Adjustment speed | 0.727 mm/s typical | ||||
Stall force | 100N | ||||
Noise level | < 35 dB(A) @ 70 N load | ||||
Valve protection and Auto-off when active but not installed on valve body | Every 6 weeks: Execute run-in sequence. On pass return to previous position. On fail enter mounting position, communicate OFF and shut down.Refer to FPORT 0x0F ON/OFF: | ||||
Antifreeze | Valve side sensor
| ||||
Accuracy of internal valve side temperature sensor | ±0.5°C | ||||
Accuracy of internal ambient temperature sensor | ±0.5ºC | ||||
Energy storage | LTO (Nominal 500mAh) | ||||
Energy generation minimum requirement | 90 days / year @ 45ºC flow pipe temperature | ||||
Conformity Radio Radio EMC EMC EU Human Exposure Product safety | CE: EN300220-2V3.1.1 & EN300220-2V3.2.1 & EN300220-1V3.1.1 EN301489-1 V2.2.3 / -3 V2.1.1 EN55014-1 / -2 EN62479 EN60335 | ||||
Radio specification | 868.0 - 868.6 MHz, 14 dBm |