...
...
Installation cycle
...
Standard
operation
...
Idle state
...
Radio failure
...
Forced heating
...
Freeze Protection
...
Comments
...
...
Valve target %
Or
Room target temperature
...
Phases between monitoring and communicating
...
Transmit messages not received by the gateway
...
Valve opens to 50%
(or remains in current position if current position is >= 50%)
...
Valve opens to 95%
...
Trigger
...
Magnetic switch.
Join accept
from Gateway,
& Device is mounted
...
Internal timer
...
Internal timer
...
From activation:
No Gateway connect
from standard operation: 6 consecutive Gateway communication failures
...
Battery voltage < 2V
...
Flow sensor raw temperature
<= 6°C
...
Radio communication interval (RCI)
...
10 seconds for 5 minutes
...
5 minutes
10 minutes
60 minutes
120 minutes
480 minutes
...
OFF
...
Three times 30 seconds
Then once 2 minutes
Then 60 minutes
...
OFF
...
OFF
...
Dynamic change of communication interval
Orah footnote | ||
---|---|---|
|
...
No
...
Yes
...
No
...
No
...
No
...
No
...
Sensors
(flow, ambient)
...
Active, every 10 seconds
...
Active
...
OFF
...
Active
...
OFF
...
Active, every
2 minutes
...
Freeze protection
...
Active, every 10 seconds
...
Active, every 150 seconds
...
OFF
...
Active, every 150 seconds
...
OFF
...
Active
...
Motor operation
...
Reference run.
Then active, according to Radio Communication
...
Active, according to
Radio Communication
...
OFF
...
Active
...
OFF
...
OFF
...
Monitoring of battery
...
Active, every 10 seconds
...
Active
...
OFF
...
Active
...
Active, every 12 hours
...
Active, every
2 minutes
...
Internal temperature controller
...
If User Mode is Set Point Ambient Temperature: active
...
If User Mode is Set Point Ambient Temperature: active
...
OFF
...
If Safety Mode is Set Point Ambient Temperature: active
...
OFF
...
OFF
...
Default upon activation and no downlinks
...
Setpoint ambient 20°C
...
Setpoint ambient 20°C
...
Setpoint ambient 20°C
...
Include Page | ||||
---|---|---|---|---|
|