To obtain an estimate of the ambient temperatureIn the following situations, the device measures will estimate the flow temperature every 5 minutes and performs a moving average across the last 30 minutes. It then performs the following computation:
...
--uriencoded--\text%7BAmbient Temperature%7D = \frac %7B\text%7BAmbient Sensor Raw Value%7D%5e%7B2.2%7D%7D %7B\text%7BFlow Sensor Raw Values Moving Average%7D%5e%7B1.2%7D%7D
If a Room Temperature was provided through a Port 0x01 Downlink within the last 10 minutes, the device uses this; otherwise, it uses the estimated room temperature as defined aboveroom temperature: Info
The device has never received an external sensor temperature
The last communicated external sensor temperature was “0”
It has been a long time since the device last received communication of an external sensor temperature (see FPORT 0x09 for adjustment of this expiry time)
The device has become disconnected from the Gateway
See FPORT 0x08 for the Temperature Estimation Algorithm, and for adjustment of the algorithm.
To achieve the instructed room temperature, the device applies the PI PID algorithm.
Mathblock | ||||
---|---|---|---|---|
| ||||
--uriencoded--e = \text%7BSetPoint Temperature%7D - \text%7BAmbient Temperature%7D |
Mathblock | ||||
---|---|---|---|---|
| ||||
--uriencoded--\text%7BValve Percent%7D\text{Valve Percent} = \text%7BPrevious Valve Percent%7D + K_p * e(t) + K_I * \sum_%7B%7D%5e%7B%7D e |
...
{}^{} e(t) + K_d * \Big( e(t)-e(t-1) \Big) + \text{Offset Percent} |
See FPORT 0x07 for adjustment of the PID coefficients and Offset Percent.
The device considers moving the motor every 5 minutes.
PID Flow Chart