Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 4 Next »

FPort Number

Type of operation

Payload length

Description

Comments

0x00

MAC Commands

8 Bytes

RESERVED

0x01

  • Valve position % mode

  • Temperature setpoint mode (°C) with flow temperature sensor

Downlink:

6 Bytes

Uplink:

11 Bytes

  • Actuator operation mode with valve position % only

  • Self-regulation mode of the flow actual temperature, using the flow requested temperature

Default upon device activation with setpoint 55°C

0x02

Report REV Number, Hardware and Firmware Version

Downlink:

n Byte(s)

Uplink:

6 Bytes

Request REV Number, Hardware and Firmware Version from MLR003FiEU61-12-1.2

Only supported in radiator product series MLR003R.

0x03 

 Motor operating range

Downlink:

1 Byte

Uplink:

1 Byte

Set/change motor operating range (mm) from default value 2,56mm

Only supported in radiator product series MLR003R.

0x04 

 LoRa Spread Factor

Downlink:

1 Byte

Uplink:

1 Byte

 Set/change LoRa spread factor from default value

Only supported in radiator product series MLR003R.

0x05

Slow Harvesting (SH) and Valve opening point detection OPD)

Downlink:

1 Byte

Uplink:

1 Byte

Activate and report OPD, activate/deactivate Slow Harvesting

Only supported in radiator product series MLR003R.


  • No labels