Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 2 Next »

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.0

8

0

SPV

Set Point Value according to User Mode

VALVE %: 0x00 … 0x64 / 0 … 100%

Res = 1%

FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C

0x00 = Default = 0x6E = 55°C

Res = 0,5°C

2

DB1.7…1.0

8

8

 

RESERVED

Set to 0x00

3

DB2.7…2.0

8

16

SSV

Set Safety Value according to safety mode

FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C

0x00 = Default = 0x6E = 55°C

Res = 0,5°C

VALVE %: 0x00 … 0x64 / 0 … 100%

Res = 1%

4

DB3.7

1

24

 

RESERVED

 

DB3.6…3.4

3

25

RCI

Radio Communication Interval

0b000 = Default = 15 minutes

0b000

15 minutes

0b001

5 minutes

0b010

60 minutes

0b011

120 minutes

0b100

480 minutes

0b101

RESERVED

0b110

RESERVED

0b111

RESERVED

 

DB3.3…3.2

2

28

UM

User Mode

0b01 = Default = SP Flow Temperature

0b00

Valve Position %

0b01

SP Flow Temperature °C

0b10

RESERVED

0b11

RESERVED

 

DB3.1…3.0

2

30

SM

Safety Mode

0b01 = Default = SP Flow Temperature

0b00

RESERVED

0b01

SP Flow Temperature °C

0b10

Valve Position %

0b11

RESERVED

5

DB4.7…4.0

8

32

RESERVED

 6

DB5.7

1

40

REF 

Do Reference Run now

Default = 0

 

DB5.6…5.5

2

41

GAIN

Proportional Controller Gain

0b10 = Default = 1

0b00

3

0b01

4

0b10

1

0b11

2

 

DB5.4…5.0

5

43

 

RESERVED

  • No labels