Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 19 Next »

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.0

8

0

SPV

Set Point Value according to User Mode

VALVE %: 0x00 … 0x64 / 0 … 100%

Res = 1%

AMB TEMP: 0x00 … 0x50 / 0 … 40°C

0x00 = Default = 0x26 = 19°C

Res = 0,5°C

2

DB1.7…1.0

8

8

 RT

Room TMP from RCU °C

0x00 … 0xA0 / 0 … 40°C

0x00 = No Room TMP provided

Res = 0,25°C

3

DB2.7…2.0

8

16

SSV

Set Safety Value according to safety mode

AMB TEMP: 0x00 … 0x50 / 0 … 40°C

0x00 = Default = 0x26 = 19°C

Res = 0,5°C

VALVE %: 0x00 … 0x64 / 0 … 100%

Res = 1%

4

DB3.7

1

24


RESERVED

 

DB3.6…3.4

3

25

RCI

Radio Communication Interval

0b000 = Default = 10 minutes

0b000

10 minutes

0b001

5 minutes

0b010

60 minutes

0b011

120 minutes

0b100

480 minutes

0b101

RESERVED

0b110

RESERVED

0b111

RESERVED

 

DB3.3…3.2

2

28

UM

User Mode

0b10 = Default = SP Ambient Temperature

0b00

Valve Position %

0b01

RESERVED

0b10

SP Ambient Temperature °C

0b11

RESERVED

 

DB3.1…3.0

2

30

SM

Safety Mode

0b00 = Default = SP Ambient Temperature

0b00

SP Ambient Temperature °C

0b01

RESERVED

0b10

Valve Position %

0b11

RESERVED

5

DB4.7…4.4

4

32

FSOC

Offset Compensation Flow Sensor °C

-8°C … +7°C

0x00

+3°C (default)

0x01

+1°C

0x02

+2°C

0x03

+3°C

0x04

+4°C

0x05

+5°C

0x06

+6°C

0x07

+7°C

0x08

-8°C

0x09

-7°C

0x0A

-6°C

0x0B

-5°C

0x0C

-4°C

0x0D

-3°C

0x0E

-2°C

0x0F

-1°C

 

DB4.3…4.0

4

36


RESERVED

6

DB5.7

1

40

REF

Do Reference Run now

Default = 0

 

DB5.6…5.0

7

41


RESERVED


  • No labels