DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.0

8

0

 

 

 

 

 

 

 

 

EXP

 

 

 

 

 

 

 

 

External Temperature Sensor expiry.

If a Room Temperature is sent by Downlink, continue using it until:

a new Room Temperature is sent by Downlink, or until

the Device loses Gateway communication, or until

0x00

no expiry

x > 0x00

5 * x minutes pass

Default = 0x30 = 4 hours

Tip: To get Temperature Sensor details without changing any options, send an empty FPORT 0x09 Downlink.

 

UPLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.0

8

0

 

 

 

 

 

 

 

 

EXP

 

 

 

 

 

 

 

 

External Temperature Sensor expiry.

If a Room Temperature is sent by Downlink, it will be used until:

a new Room Temperature is sent by Downlink, or until

the Device loses Gateway communication, or until

0x00

no expiry

x > 0x00

5 * x minutes pass

2

DB1.7

1

8

RTS

Source of Room Temperature value used for Temperature Control

0x00

Device is using internal temperature estimation algorithm

0x01

Device is using most recently provided external temperature sensor value

DB1.6…1.0

7

9

RESERVED