Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 8 Next »

DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.0

8

0

FADD

Flow Raw Value Offset

With 2’s complement

Res = 0.25°C

0x00

0.00

0x01

0.25

0x02

0.50

0x7F

31.75

0x80

-32.00

0xFF

-0.25

2

DB1.7…1.0

8

8

 FMUL

Flow Raw Value Multiplication

Res = 0.01°C

3

DB2.7…2.0

8

16

NFD

Number of most recent Flow Raw Temperature values to delay by (skip)

Clamped to [0..=20]

4

DB3.7…3.0

8

24

NMAF

Number of values used in calculation of Flow Moving Average

Clamped to [1..=20]

5

DB4.7…4.0

8

32

NMAA

Number of values used in calculation of Ambient Moving Average

Clamped to [1..=20]

6

DB5.7…5.0

8

40

NMAE

Number of values used in calculation of Estimate Moving Average

Clamped to [1..=20]

7

DB6.7…6.0

8

48

RATO

Ratio Offset

Res = 0.01

8

DB7.7…7.0

8

56

POW

Ratio Power

Res = 0.01

Default = 0x00 = 1.2

Tip: To get Temperature Estimation details without changing any options, send an empty FPORT 0x08 Downlink.

UPLINK

Same a Downlink, confirming Uplink settings

Recommended Settings

Scenario

Flow Offset

Flow Multiplication

Flow Delay

Flow Moving Average

Estimate Moving Average

Ratio Power

Small or well-insulated room

0.0

1.0

0 or 1

If > 0, reduce PI-Coefficient KP (see Port 7)

1.0 + small

Large or poorly-insulated room

0.0

1.0

Consider using

If > 0, reduce PI-Coefficient KP (see Port 7)

1.0 + big

Unheated Room is warm

0.0

1.0

1.0 + small

Unheated Room is cold

0.0

1.0

1.0 + big

Temperature close to the radiator is desired

0.0

1.0

1.0 + small

Temperature far from the radiator is desired

0.0

1.0

1.0 + big

Flow Temperature fluctuates

0.0

1.0

Use to smooth

Estimated Temperature fluctuates

0.0

1.0

Use to smooth

Device is mounted above an exposed pipe

Use to compensate

Use to compensate

  • No labels