Fluid (water) temperature FSRV

Recommended offset for the flow sensor value FTMP applied in FPORT 0x08

(Offset values derived in climate chamber and without valve adapter)

55°C

10°C

65°C

13°C

70°C

14°C

--uriencoded--\begin%7Balign*%7D

& \text%7BFlow Smoothened %7D F_s = \frac %7B(0.2 F + 1.2F_%7Bt-1%7D + 1F_%7Bt-2%7D + 0.8F_%7Bt-3%7D + 0.6F_%7Bt-4%7D + 0.3F_%7Bt-5%7D + 0.1F_%7Bt-6%7D) %7D %7B4.2%7D + \text%7BFlow Offset%7D
\\
\\
& \text%7Bwhere F = Flow Raw Value%7D
\\
& \text%7Bwhere Flow Offset = 0 (default)%7D
\\
\\
& \text%7Bif %7D \Big(F_s - z  \big( F_s - 0.5(F_%7Bs_%7Bt-3%7D%7D + F_%7Bs_%7Bt-4%7D%7D ) \big) \Big) < \text%7B Ambient Raw Value%7D
\\
& \text%7Bthen%7D
\\
&  \hspace%7B1cm%7D \text%7BFlow Corrected %7D F_c = \text%7BAmbient Raw Value%7D
\\
& \text%7Belse%7D
\\
& \hspace%7B1cm%7D \text%7BFlow Corrected %7D F_c = \Big(F_s - z * \big( F_s - 0.5(F_%7Bs_%7Bt-3%7D%7D + F_%7Bs_%7Bt-4%7D%7D ) \big) \Big) 
\\
\\
& \text%7Bwhere z = 0.1%7D
\\
\\

& \textbf%7BAmbient Temperature Estimate%7D = \textbf%7BAmbient Raw Value%7D * \Bigg( \frac%7B\textbf%7BAmbient Raw Value%7D%7D%7B\textbf%7BFlow Corrected %7D F_c%7D \Bigg) %5e%7B1.2%7D
\end%7Balign*%7D

Byte

Uplink in FPORT #1

Details

Description

2

FSRV

Flow Sensor Raw Value

The uncompensated flow temperature measured at the valve side

3

FTMP

Flow Temperature Value

The flow moving average, with offset applied

Moving Average of Flow Sensor Raw Value + OFFSET (set via FPORT 0x08)

Default OFFSET = 0

4

ASRV

Ambient Sensor Raw Value

The uncompensated ambient sensor value

5

ATMP

Ambient Temperature Value

Ambient Temperature calculated from

FPORT 0x01 Downlink Byte 2 Room Temperature (RT) value

Temperature Value

0

Use internal Ambient Temperature (ATMP) estimate

Room Temperature from external sensor

Use the room temperature value from the external sensor

In order to achieve a Set Point Value (SPV) Ambient Temperature, the device applies a PID control algorithm.

MLR003R_Ambient_and_Flow_Temperatures.png