MLR003R: FPORT 0x06: Temperature Drop Detection

Device will only check for a Temperature Drop and respond to the Detection of a Temperature Drop when the Radio Communication Interval is 5 minutes or 10 minutes

The temperature drop measurement to detect >=1,5°C on the ambient raw sensor is done only in intervals of 10minutes.

DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.6

2

0

TDA

Temperature Drop Action

Default = 0b00 = Take No Action

Upon Detection of a Temperature Drop:

0b00

Take No Action

0b01

RESERVED

0b10

close to 0% for 30 minutes and then resume normal operation

0b11

close to 0% for 60 minutes and then resume normal operation

 

DB0.5

1

2

TDB

Upon Resumption of Normal Operation:

0

Do not Beep

1

Beep

 

DB0.4

1

3

TDP

Temperature Drop Period

Activation of Temperature Drop Action after at least:

0

one temperature drop

1

two consecutive temperature drops

 

DB0.3…0.0

4

4

 

RESERVED

 

To receive an Uplink without changing any settings, send an empty Downlink.

 

UPLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.6

2

0

TDA

Temperature Drop Action

Upon Detection of a Temperature Drop, device will:

0b00

Take No Action

0b01

RESERVED

0b10

close to 0% for 30 minutes and then resume normal operation

0b11

close to 0% for 60 minutes and then resume normal operation

 

DB0.5

1

2

TDB

Upon Resumption of Normal Operation, device will:

0

not Beep

1

Beep

 

DB0.4

1

3

TDP

Temperature Drop Period

Activation of Temperature Drop Action after at least:

0

one temperature drop

1

two consecutive temperature drops

 

DB0.3…0.1

3

4

 

RESERVED

 

DB0.0

1

7

TDD

A Temperature Drop has been Detected

0

No Detection

1

Detection

Ambient RAW value dropped by >= 1.5°C during the last 10 minutes