ReMan / ReCom MVA009 (EN)
EnOcean Remote Management (ReMan), Remote Commissioning (ReCom)
EnOcean Link Table
MVA005 supports the following number of tech-in relationships:
Inbound EnOcean Link Table: 0 Teach-in relationships (not existing)
Outbound EnOcean Link Table: 3 Tech-in relationships
Comment:
MVA005 uses an outbound link table only, inbound relationships are not supported. Manually erasing the outbound link table is not possible. Manual pairing (teach-in) however overwrites the first entry of the outbound link table, clearing the other two entries.
Outbound Teach-In
Outbound teach-in is supported for EEP A5-20-06 (4BS).
Two options are available to teach-in MVA005 with an external Gateway/Controller:
Manual via teach-in message (4BS version 3)
Remote commissioning
ReMan supported functions
PING
LOCK, UNLOCK (Acknowledged)
SET CODE (Acknowledged)
QUERY ID, QUERY STATUS
Comments:
MVA005 Default Security Code = 0x53C65E34.
Invalid security codes: 0x00000000; 0xFFFFFFFF
Invalid security code settings will be automatically converted in to the default code 0x53C65E34 to ensure further access through Remote Management.
For further details, pls. refer to the document “Remote Management” by EnOcean GmbH: https://www.enocean.com/fileadmin/redaktion/pdf/tec_docs/RemoteManagement.pdf
Für weitergehende Informationen wird auf das Dokument “Remote Management” der EnOcean GmbH verwiesen: https://www.enocean.com/fileadmin/redaktion/pdf/tec_docs/RemoteManagement.pdf
ReCom Standard Functions
Remote Commissioning Mandatory Commands Bundle:
Remote Commissioning Acknowledge
Get Product ID Query & Response
EnOcean Link Table Basic Commands Bundle
Get Link Table Metadata Query & Response
Get Link Table Query & Response
Set Link Table Content
Configuration Parameters Bundle
Get Device Configuration Query & Response
Set Common Configuration Query
RESET DEVICE DEFAULTS *1
*1RESET DEVICE DEFAULTS:
Immediately after executing the Reset_To_Defaults command, the device is reset to the manufacturer status and restarted. The internal memory is reset (1x red LED) and the drive is started (2x red LED). The manufacturer default parameters are reloaded (see Table 9.5 "DEFAULT" values). The motor then moves to the mounting position and performs a reference run. When installed, the drive is started in the maintenance interval. Unmounted, the drive remains in the mounting position and shuts off. All entries of the link table and the security code remain unaffected
ReCom internal MVA Parameter
Device description file (DDF, xml) can be found here Overview MVA EnOcean
Description INDEX 0 = Ambient to Target Offset [K]
The ambient to target offset parameter [K] is related to a function to correct the ambient temperature measured in the actuator. Due to its mechanical design and the near field of the radiator, the temperature measured is subject to deviations relative to the actual room temperature. In automatic mode (0x00), the drive uses its integrated flow sensor (valve adapter) to determine the actual room temperature value with its internal approximation function. In all other settings than automatic mode, an absolute value is subtracted from or added to the effective measured temperature. Example setting 0x07 = +3K: The temperature output by the ambient sensor is the effectively measured temperature minus 3°C.
Description INDEX 1 = Radio communication interval [s/min]
The radio interval is only relevant when operating in radio communication failure mode (RCE, or controller disabled) and controls the transmit interval of 4BS standard telegrams according to A5-20-06. In standard operation, the 4BS defined radio interval will always override the parameter internal setting.
Description INDEX 6 = buzzer
Buzzer is used for versioning in some firmware versions; it has no additional function. It is readable but not writable (section 11).
Description INDEX 11 = Ambient to Target Offset (A) Parameter
The so-called “A” parameter is used within the internal temperature approximation function to calculate ambient temperature corrections based on actual measured flow (valve adapter) temperatures. In steady sensor state, the A factor describes the level of parallel shift of the ambient temperature. Function [T Approximated = T Ambient - ((T Flow - T Ambient) * Offset A Parameter)]. Differences in time constants when radiators are turned on and off are compensated with an overlaying smoothing function to eliminate temperature peaks. The smoothing function is based 2 internal arrays with 3 consecutive temperature values that are compared in its deviations (<1°C) over a time period of 3 x 10 minutes.
Description INDEX 12 = Temperature Control Gain „P“ Parameter (only when SPS = 1)
The P parameter describes the gain/multiplier within the temperature control loop (only when SPS = 1) to calculate the valve adjustment % value. The default value of 90 corresponds to a valve opening of 18% when T Ambient the Setpoint temperature difference is 1°C. Note: The Automatic Ambient to Target Offset (Index 0 = 0x00) mode does us the approximated temperature to calculate the valve opening value, which is why the corresponding valve opening angles may be different to the above mentioned calculated value.
Description INDEX 14 = Signal Communication Interval
The signal communication interval can be changed from its default value of 12 hours to carry out Remote commissioning operations with short(er) time intervals.
ReCom Device Parameter | INDEX | Description |
Ambient to Target Offset [K] | 0 | (0x00) 0 … Auto* (DEFAULT) (0x01) 1 … -3 K (0x02) 2 … -2 K (0x03) 3 … -1 (0x04) 4 … 0 K (0x05) 5 … +1 K (0x06) 6 … +2 K (0x07) 7 … +3 K … (0x0F) 15 … +11 K |
Radio communication interval [s/min] | 1 | (0x00) 0…Auto * (DEFAULT) (0x01) 1 … 10sec (For debug only) (0x02) 2 … 2min (0x03) 3 … 5min (0x04) 4 … 10 min (0x05) 5 … 20min (0x06) 6 … 30min
|
Buzzer | 6 | Without function, read-only
DEFAULT 0x00 |
Execute reference run | 10 | 0x01
DEFAULT 0x00 |
Ambient to Target Offset (A) Parameter | 11 | (0x00 … 0xFF) 0 … 255
MVA005 DEFAULT DEZ 56 = HEX 0x38 |
Temperature Control Gain „P“ Parameter
| 12 | (0x00 … 0xFF) 0 … 255
DEFAULT DEZ 90 = HEX 0x5A |
Internal storage voltage (V) | 13 NUR LESEN | (0x00 … 0xFF) 0 … 255
Example: HEX 0x21 = DEZ 33 : 10 = 3,3 Volt |
Signal communication cycle
NOTE: Setting of summer bit (8h 4BS communication cycle) does not change the SIGNAL telegram cycle.
| 14 | 0x00 … 1min 0x01 … 5min 0x02 … 10min 0x03 … 20min 0x04 … 60min 0x05 … 120min 0x06 … 240min 0x07 … 360min 0x08 … 720min 0x09 … 1440min
Default: 720min (12h) |