Defaults

Changed through downlink

P coefficient

20

15

I coefficient

1,5

1,5

D coefficient

0

0

Correction factor z

D coefficient when closed

0

0

Closed percent

0

0

Offset percent

0

0

Style

Standard Style

Unchanged = Default

Integral unwind (do_back calculate)

False

Unchanged = Default

Motor operating range

1.872 mm

Unchanged = Default

Firmware

2024.08.08.02

The FTMP value is the flow smoothened term (Cs from your formula)

FTMP = (0,2C + 1,2Ct-1 + 1Ct-2 +0,8Ct-3 + 0,6Ct-4 + 0,3Ct-5  +0,1Ct-6 ) / 4,2

The ATMP value is the Ambient Estimate calculated based on your formula

ATMP = B * ( B/ Cc) ^ 1,2

where B = Ambient Raw

Cc = Flow corrected