Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 11 Current »

DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.0

8

0

KP

P Coefficient

0 … 255

Default = 0x14 = 20

Resolution = 1

2

DB1.7…1.0

8

8

KI

I Coefficient

0 … 5.12

Default = 0x4B = 1.5

Resolution = 0.02

3

DB2.7…2.0

8

16

KD

D Coefficient

0 … 51.2

Default = 0x00 = 0

Resolution = 0.2

4

DB3.7

8

24

Operating Style

1: Standard PID Controller

DB3.6…3.0

25

RESERVED

5

DB4.7…4.0

8

32

CP

Closed Percent

Minimum percent that device will close to

Default = 0%

6

DB5.7…5.0

8

40

KD0

D Coefficient when closed

0 … 51.2

Default = 0x00 = 0.0

Resolution = 0.2

7

DB6.7…6.0

8

40

OFP

Offset Percent

Percentage Offset to be added to PID Output

Default = 0x00 = 0%

To receive an Uplink without changing any settings, send an empty Downlink.

UPLINK

Same as Downlink, confirming settings.

  • No labels