Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Next »

Parameter

Range

Ambient operating temperature

0 to 40°C, max 70% rH

Flow pipe temperature

75°C max

Transportation & storage temperature range

-20 to +65°C, max 70% rH

Dimensions (LWH)

83 x 60 x 64 mm (63 x 60 x 64 without valve connector)

Weight

280 g (not including packing)

Operation at high altitude

Max 2000 m / 6500 ft above sea level

Max pin stroke (calibration range)

> 5.5 mm

Operating pin stroke (0-100%)

2.56 mm typical

Pin Stroke Resolution

Steps of 1%

Adjustment speed

0.727 mm/s typical

Stall force

140N

Noise level

< 35 dB(A) @ 70 N load

Radio Communication Interval (default)

10 minutes

Radio Communication Interval during Installation Cycle

10 seconds for 5 minutes

Radio Communication attempt Interval (after join fail or 6 consecutive communication fails)

3 * 10 seconds

Then 2 minutes

Then 60 minutes

Valve protection and Auto-off when active but not installed on valve body

Every 6 weeks: Execute run-in sequence.

On pass return to previous position.

On fail enter mounting position, communicate OFF and shut down.

Antifreeze

Valve side sensor <= 6°C

 

Safe position default

Depending on Safety Mode:

Either default temperature setpoint

Or default valve position

Default: Setpoint Flow 57°C

Operating Modes

 

Valve Position [%]

Target Flow Temperature (°C)

Default: Setpoint Flow Temperature (°C)

Accuracy of internal valve side temperature sensor

±0.5°C

Accuracy of internal ambient temperature sensor

±0.5ºC

 

Default offset of internal valve-side temperature sensor

+5K

(Added to the raw sensor value FSRV)

Energy storage

LTO (Nominal 500mAh)

Energy generation minimum requirement

90 days / year @ 45ºC flow pipe temperature

Battery voltage flag (ES)

Battery-low flag will be set

when battery voltage drops below 2.3V

Conformity

Radio

Radio EMC

EMC

EU Human Exposure

Product safety

CE:

EN300220-2V3.1.1 & EN300220-2V3.2.1 & EN300220-1V3.1.1

EN301489-1 V2.2.3 / -3 V2.1.1

EN55014-1 / -2

EN62479

EN60335

Radio specification

868.0 - 868.6 MHz, 14 dBm

  • No labels