Copyright Micropelt

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 7 Next »

DOWNLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7…0.5

3

0

RESERVED

DB0.4

1

3

OPR

Opening Point Reset

1 = Reset Opening Point:

Device will set Opening Point Percent to Not Found.

When it is appropriate for the device to do so, the device will re-find the Opening Point Percent.

DB0.3…0.2

2

4

HW

Hot Water Availability

0b00

Use time of year to determine whether hot water is available

0b01

Hot water is off

0b10

Hot water is on

0b11

RESERVED

DB0.1…0.0

2

6

SH

Slow Harvesting

0b00

Default Opening Point Detection and Slow Harvesting

0b01

Do Opening Point Detection and Slow Harvesting now

0b10

Do Opening Point Detection now

Disable Slow Harvesting

0b11

Disable Opening Point Detection

Disable Slow Harvesting

2

DB1.7

1

8

RESERVED

DB1.6…1.0

7

9

MAX

Maximum Flow Sensor Raw Temperature °C

0x00 … 0x42 / 0 … 33°C

0x00 = Default = 0x34 = 26°C

Res = 0.5°C

UPLINK

BYTE

BIT RANGE

SIZE

OFFSET

ABBREVIATION

DETAILS

1

DB0.7

1

0

OPF

Opening Point Percent has been found

0

Not Found

1

Found

DB0.6…0.0

7

1

OP

Opening Point Percent

0x00 … 0x64 / 0 … 100%

Res = 1%

2

DB1.7…1.3

5

8

RESERVED

DB1.2…1.0

3

13

SH

Slow Harvesting Status

0b000

Not Slow Harvesting because Slow Harvesting is switched off in Downlink

0b001

Not Slow Harvesting because recently target % ≠ 0%

0b010

Not Slow Harvesting because hot water is expected to be off

0b011

Cannot detect Opening Point

0b100

Not Slow Harvesting because battery is high

0b101

Not Slow Harvesting because Slow Harvesting was attempted but generated insufficient current

0b110

Detecting Opening Point

0b111

Slow Harvesting

  • No labels