BYTE
...
BIT RANGE
...
SIZE
...
OFFSET
...
ABBREV.
...
DETAILS
...
1
...
DB0.7…0.0
...
8
...
0
...
SPV
...
Set Point Value according to User Mode
VALVE %: 0x00 … 0x64 / 0 … 100%
Res = 1%
FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C
0x00 = Default = 0x6E = 55°C
Res = 0,5°C
...
2
...
DB1.7…1.0
...
8
...
8
...
...
RESERVED
Set to 0x00
...
3
...
DB2.7…2.0
...
8
...
16
...
SSV
...
Set Safety Value according to safety mode
FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C
0x00 = Default = 0x6E = 55°C
Res = 0,5°C
VALVE %: 0x00 … 0x64 / 0 … 100%
Res = 1%
...
4
...
DB3.7
...
1
...
24
...
...
RESERVED
...
...
DB3.6…3.4
...
3
...
25
...
RCI
...
Radio Communication Interval
0b010 = Default = 60 minutes
...
0b000
...
10 minutes
...
0b001
...
5 minutes
...
0b010
...
60 minutes
...
0b011
...
120 minutes
...
0b100
...
480 minutes
...
0b1zz
...
RESERVED
...
...
DB3.3…3.2
...
2
...
28
...
UM
...
User Mode
0b01 = Default = SP Flow Temperature
...
0b00
...
Valve Position %
...
0b01
...
SP Flow Temperature °C
...
0b10
...
RESERVED
...
0b11
...
RESERVED
...
...
DB3.1…3.0
...
2
...
30
...
SM
...
Safety Mode
0b01 = Default = SP Flow Temperature
...
0b00
...
RESERVED
...
0b01
...
SP Flow Temperature °C
...
0b10
...
Valve Position %
...
0b11
...
RESERVED
...
5
...
DB4.7…4.4
...
4
...
32
...
FSOC
...
Offset Compensation Flow Sensor °C
-8°C … +7°C
...
0x00
...
+5°C (default)
...
0x01
...
+1°C
...
0x02
...
+2°C
...
0x03
...
+3°C
...
0x04
...
+4°C
...
0x05
...
+5°C
...
0x06
...
+6°C
...
0x07
...
+7°C
...
0x08
...
-8°C
...
0x09
...
-7°C
...
0x0A
...
-6°C
...
0x0B
...
-5°C
...
0x0C
...
-4°C
...
0x0D
...
-3°C
...
0x0E
...
-2°C
...
0x0F
...
-1°C
...
...
DB4.3…4.0
...
4
...
36
...
...
RESERVED
...
6
...
DB5.7
...
1
...
40
...
REF
...
Do Reference Run now
Default = 0
...
...
DB5.6…5.5
...
2
...
41
...
GAIN
...
Proportional Controller Gain
0b10 = Default = 1
...
0b00
...
3
...
0b01
...
4
...
0b10
...
1
...
0b11
...
2
...
...
DB5.4…5.0
...
5
...
43
...
...