BYTE

BIT RANGE

SIZE

OFFSET

ABBREV.

DETAILS

1

DB0.7…0.0

8

0

SPV

Set Point Value according to User Mode

VALVE %: 0x00 … 0x64 / 0 … 100%

Res = 1%

FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C

0x00 = Default = 0x6E = 55°C

Res = 0,5°C

2

DB1.7…1.0

8

8

 

RESERVED

Set to 0x00

3

DB2.7…2.0

8

16

SSV

Set Safety Value according to safety mode

FLOW TEMP: 0x00 … 0xA0 / 0 … 80°C

0x00 = Default = 0x6E = 55°C

Res = 0,5°C

VALVE %: 0x00 … 0x64 / 0 … 100%

Res = 1%

4

DB3.7

1

24

 

RESERVED

 

DB3.6…3.4

3

25

RCI

Radio Communication Interval

0b010 = Default = 60 minutes

0b000

10 minutes

0b001

5 minutes

0b010

60 minutes

0b011

120 minutes

0b100

480 minutes

0b1zz

RESERVED

 

DB3.3…3.2

2

28

UM

User Mode

0b01 = Default = SP Flow Temperature

0b00

Valve Position %

0b01

SP Flow Temperature °C

0b10

RESERVED

0b11

RESERVED

 

DB3.1…3.0

2

30

SM

Safety Mode

0b01 = Default = SP Flow Temperature

0b00

RESERVED

0b01

SP Flow Temperature °C

0b10

Valve Position %

0b11

RESERVED

5

DB4.7…4.4

4

32

FSOC

Offset Compensation Flow Sensor °C

-8°C … +7°C

0x00

+5°C (default)

0x01

+1°C

0x02

+2°C

0x03

+3°C

0x04

+4°C

0x05

+5°C

0x06

+6°C

0x07

+7°C

0x08

-8°C

0x09

-7°C

0x0A

-6°C

0x0B

-5°C

0x0C

-4°C

0x0D

-3°C

0x0E

-2°C

0x0F

-1°C

 

DB4.3…4.0

4

36

 

RESERVED

6

DB5.7

1

40

REF

Do Reference Run now

Default = 0

 

DB5.6…5.5

2

41

GAIN

Proportional Controller Gain

0b10 = Default = 1

0b00

3

0b01

4

0b10

1

0b11

2

 

DB5.4…5.0

5

43

 

RESERVED