Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Comment: Fix upper bound.
Also be consistent with decimal point style.

BYTE

BIT RANGE

SIZE

OFFSET

ABBREV.

DETAILS

1

DB0.7…0.0

8

0

CVP

Current Valve Position %

0x00 … 0x64 / 0 … 100%

Res = 1%

2

DB1.7…1.0

8

8

FSRV

Flow Sensor RAW Value °C

0x00 … 0xFF / 0 … 125127.0°C5°C

Res = 0.5°C

3

DB2.7…2.0

8

16

FTMP

Flow TEMPERATURE Value °C

Orah footnote
textFlow Temperature Value is (moving average of Flow Raw Value since last radio communication) + offset correction

0x00 … 0xFF / 0 … 125127.0°C5°C

Res = 0.5°C

4

DB3.7…3.0

8

24

ASRV

Ambient Sensor RAW Value °C

0x00 … 0xFF / 0 … 63.75°C

Res = 0.25°C

5

DB4.7…4.0

8

32

ATMP

Ambient TEMPERATURE Value °C

Orah footnote
textAmbient Temperature Value is Ambient Temperature Estimate, used in Temperature Control Algorithm

0x00 … 0xFF / 0 … 63.75°C

Res = 0.25°C

6

DB5.7

1

40

 

RESERVED

 

DB5.6

1

41

ES

Energy Storage is low

1 = Battery is low

 

DB5.5

1

42

HA

Harvesting

1 = Harvesting is active

 

DB5.4

1

43

ASF

Ambient Sensor Failure

1 = Sensor Failure

 

DB5.3

1

44

FSF

Flow Sensor Failure

1 = Sensor Failure

 

DB5.2

1

45

RCE

Radio Communication Error

1 = Radio Loss

Orah footnote
textDevice was not able to join the network server, or an uplink message did not receive an acknowledge

 

DB5.1

1

46

RSS

Radio Signal Strength

0 = Normal Radio Signal (RSSI is greater than -100 dBm)

1 = Weak Radio Signal (RSSI is less than -100 dBm)

 

DB5.0

1

47

ME

Motor

1 = Motor Error

7

DB6.7…6.0

8

48

STV

Storage Voltage V

0x00 … 0xFF / 0 … 5100mV

Res = 20mV

8

DB7.7…7.0

8

56

ACC

Average Current Consumed

0x00 … 0xFF / 0 … 2550µA

Res = 10µA

9

DB8.7…7.0

8

64

ACG

Average Current Generated

Orah footnote
textMomentary charge current generated (assuming this has been fairly constant for the past RCI)

0x00 … 0xFF / 0 … 2550µA

Res = 10µA

10

DB9.7

1

72

OFF

Operating Condition

0 = Device is in Normal Operation and is Active

1 = Device is in Mounting Position and OFF

 

DB9.6

1

73

SFC

Storage Fully Charged

1 = Fully Charged

 

DB9.5

1

74

 

RESERVED

 

DB9.4

1

75

REFC

Reference Run Completed

1 = Successfully Completed

 

DB9.3

1

76

 

RESERVED

 

DB9.2…9.0

3

77

UM

User Mode

As set by the last received Downlink (DB3.3…3.2)

 

0b000

Valve Position %

0b001

RESERVED

0b010

SP Ambient Temperature °C

0b011

Detecting Opening Point

0b100

Slow Harvesting

0b1zz

RESERVED

11

DB10.7…10.0

8

80

UV

User Value according to User Mode

As set by the last received Downlink (DB0.7…0.0)

VALVE %: 0x00 … 0x64 / 0 … 100%

Res = 1%

AMB TEMP: 0x00 … 0x50 / 0 … 40°C

Res = 0,.5°C

If Detecting Opening Point or Slow Harvesting, this value is the maximum flow temperature:

MAX FLOW TEMP: 0x00 … 0x84 / 0 … 33°C

Res = 0,.25°C


Orah footnotes display